| Notes |
| Date |
Text |
| 2016-03-10 11:44:11 | MECHANICAL PROVISO | | | 3/10/16 | | | | | | 1) WIND LOAD ENGINEERING FOR TIE DOWN AND ATTACHMENT OF | | | THE CU, RTU'S, CURBS AND STANDS SHALL BE SUBMITTED TO | | | THE BUILDING DEPARTMENT FOR REVIEW AND APPROVAL PRIOR | | | TO 1ST INSPECTION. | | | 2) VALUE INCREASE ON PERMIT APPLICATION REQUIRED FOR | | | COST OF LARGER 1ST FLOOR AC SYSTEM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|