| Plan Review Notes For Permit 15090732 |
| Permit Number |
15090732 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-02-05 17:21:42 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15090732 | | | 2/5/16 | | | | | | 1) THE HEAT LOAD SUMMARY ON SHEET M-1 IS INCOMPLETE AND | | | SHALL BE SUBMITTED ON A SEPARATE SIGNED AND SEALED | | | SUMMARY SHEET- REFER TO SECTION 503.2.1 FBC-10 ENERGY | | | CONSERVATION (EXCEPTION): | | | WHERE MECHANICAL SYSTEMS ARE DESIGNED BY A REGISTERED | | | ENGINEER, THE ENGINEER HAS THE OPTION OF SUBMITTING A | | | SIGNED AND SEALED SUMMARY SHEET TO THE BUILDING | | | DEPARTMENT IN LIEU OF THE COMPLETE SIZING | | | CALCULATION(S). SUCH SUMMARY SHEET SHALL INCLUDE THE | | | FOLLOWING (BY ZONE): | | | 1. PROJECT NAME/OWNER | | | 2. PROJECT ADDRESS | | | 3. AREA IN SQUARE FEET | | | 4. SIZING METHOD USED | | | 5. OUTDOOR DRY BULB USE | | | 6. INDOOR DRY BULB | | | 7. OUTDOOR WET BULB USED | | | 8. GRAINS WATER (DIFFERENCE) | | | 9. TOTAL SENSIBLE GAIN | | | 10. TOTAL LATENT GAIN | | | 11. RELATIVE HUMIDITY | | | 12. TOTAL COOLING REQUIRED WITH OUTSIDE AIR | | | 13. TOTAL HEATING REQUIRED WITH OUTSIDE AIR | | | 2) UNDER THIS REVISION, PLEASE CLARIFY HOW THE THE HEAT | | | LOAD HAS INCREASED FROM 131 MBH TO 230 MBH COOLING , | | | AND 35.8 TO 83 MBH HEATING WHEN THERE APPEARS TO BE NO | | | APPARENT CHANGE IN THE ZONE, THE OCCUPANT LOAD, OR THE | | | OUTSIDE AIR INTAKE. | | | 3) DUE TO THE CHANGE IN THE 1ST FLOOR AC SYSTEM, A | | | REVISED ENERGY CALCULATION FORM 506-2010 MUST BE | | | SUBMITTED. | | | 4) PROVIDE AN AIR BALANCE CALCULATION ON THE PLAN. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|