Notes
Date Text
2015-10-06 11:41:491ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15090715
 10/6/15
  
 1) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES OF THE NEW TENANT OCCUPANCY- REFER TO
 TABLE 403.3 FBC-14 MECHANICAL AND SHOW THE REQUIRED AND
 PROVIDED CFM'S OF OUTSIDE AIR. INDICATE HOW THE O/A
 WILL BE CONTROLLED PER SECTION C403.2.4.4 FBC-14 ENERGY
 CONSERVATION.
 2) THE SUBMITTED AC CALCULATIONS ARE FOR COOLING ONLY.
 PLEASE PROVIDE DESIGN HEATING LOADS- REFER TO SECTION
 309.1 FBC-14 MECHANICAL.
  
  