| Plan Review Notes For Permit 15090715 |
| Permit Number |
15090715 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-10-06 11:41:49 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15090715 | | | 10/6/15 | | | | | | 1) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES OF THE NEW TENANT OCCUPANCY- REFER TO | | | TABLE 403.3 FBC-14 MECHANICAL AND SHOW THE REQUIRED AND | | | PROVIDED CFM'S OF OUTSIDE AIR. INDICATE HOW THE O/A | | | WILL BE CONTROLLED PER SECTION C403.2.4.4 FBC-14 ENERGY | | | CONSERVATION. | | | 2) THE SUBMITTED AC CALCULATIONS ARE FOR COOLING ONLY. | | | PLEASE PROVIDE DESIGN HEATING LOADS- REFER TO SECTION | | | 309.1 FBC-14 MECHANICAL. | | | | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|