| 2015-10-30 06:27:05 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15090696 |
| | ADD: 5200 N. FLAGLER DR. SUITE # 2006 |
| | CONT: A & A DEVELPOMENT |
| | TEL: (561)719-0895 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: FRI. OCT.30/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) THE PERMIT APPLICATION AND PLANS BOTH INDICATE NEW |
| | 24 X 24 INCH TILE FLOORING. PLANS ALSO INDICATE THE USE |
| | OF 1/4 INCH CORK FLOOR UNDERLAYMENT. |
| | PLEASE SUBMIT TEST REPORTS NOT JUST RESULTS OF THE |
| | TEST. NOTE EACH OF THE SOUND TEST HAVE 8 TO 10 PAGES |
| | AND THE FLAME SPREAD TEST MAY HAVE AS MANY AS 15 PAGES |
| | WITHIN THE REPORT. THE REASON WE REQUEST THE REPORT IS |
| | FOR AT WHAT THICKNESS OF THE SLAB WAS THE CONCRETE SLAB |
| | TESTED, OR WAS IT A WOOD FLOOR/ TRUSS SYSTEM. |
| | THE OTHER ISSUE IS ALOT OF MANUFACTURERS HAD THEIR |
| | PRODUCT TESTED WITH DROPPED CEILINGS LOADED WITH |
| | INSULATION WHICH IS NOT ACCEPTABLE. |
| | |
| | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| | 2014) |
| | |
| | 1A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 1B) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 2) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |