| 2015-10-02 09:03:01 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE SECOND ELECTRICAL REVIEW OF |
| | THE ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH |
| | REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE |
| | REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED |
| | SHALL BE RESUBMITTED FOR ANOTHER REVIEW. |
| | |
| | 1. PER THE CITY OF WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CONSTRUCTION DOCUMENTS SHALL BE SUBMITTED IN |
| | ACCORDANCE WITH SECTIONS 107.2.1 THROUGH 107.2.5. IN A |
| | NUT SHELL, THE PLANS HAVE TO DEFINE THE SCOPE OF WORK |
| | AS YOU HAVE BUT THE MINIMUM ALLOWABLE SCALE IS 1/8?. |
| | THE PERSON RESPONSIBLE FOR THE DESIGN SHALL INCLUDE |
| | THEIR NAME AND SIGNATURE. |
| | 2. YOU SHALL INDICATE ON THE PLANS WHERE THE WORK IS TO |
| | BE DONE. THE ELECTRICAL PERMIT APPLICATION INDICATES |
| | NEW LIGHTING IN THE KITCHEN AND BATH YET THE SCOPE AS |
| | DEFINED ON THE PLAN ONLY ADDRESSES REPLACEMENT |
| | RECEPTACLES. |
| | 3. NEC 406.4(D) HAS SPECIFIC REQUIREMENTS FOR |
| | REPLACEMENT RECEPTACLES WHICH SHALL BE ADHERED TO. |
| | ARTICLE 410 HAS THE SAME FOR THE NEW LUMINARIES. |
| | 4. ALL NEW LIGHTING SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE 5TH EDITION OF THE FBC-ENERGY CONSERVATION 2014. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU |
| | |