| 2015-09-30 18:19:49 | APPROVED WITH EXCEPTION |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). |
| | 1) FBC-R - M1305.1.3 APPLIANCES IN ATTICS. ATTICS |
| | CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN OPENING |
| | AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE ENOUGH TO |
| | ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT NOT LESS |
| | THAN 30 INCHES (762 MM) HIGH AND 22 INCHES (559 MM) |
| | WIDE AND NOT MORE THAN 6 FEET (1829 MM) LONG MEASURED |
| | ALONG THE CENTERLINE OF THE PASSAGEWAY FROM THE OPENING |
| | TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE CONTINUOUS |
| | SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5 NOT LESS |
| | THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE SPACE AT |
| | LEAST 30 INCHES (762 MM) DEEP AND 30 INCHES (762 MM) |
| | WIDE SHALL BE PRESENT ALONG ALL SIDES OF THE APPLIANCE |
| | WHERE ACCESS IS REQUIRED. THE CLEAR ACCESS OPENING |
| | DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY 30 INCHES |
| | (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW REMOVAL |
| | OF THE LARGEST APPLIANCE. |
| | 2) FBC-R - M1305.1.3.1 ELECTRICAL REQUIREMENTS. A |
| | LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE |
| | REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET |
| | SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN |
| | ACCORDANCE WITH CHAPTER 34. |
| | |