| Plan Review Notes For Permit 15090657 |
| Permit Number |
15090657 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-11-07 06:38:47 | 1)SUBMIT COMBUSTION AIR CALCULATIONS FOR ALL GAS | | | APPLIANCES LOCATED ON THE INTERIOR OF THE STRUCTURE. | | | COMPLY W/2010 FBC-RESIDENTIAL SEC.G2407.1 & G2407.5 | | | THROUGH G2407.11. | | | 2) SUBMIT TWO COPIES OF THE MANUF. SPECIFICATIONS. IT | | | APPEARS ONLY ONE COPY HAS BEEN SUBMITTED. WPB AMEND. TO | | | FBC SEC. 107.1. | | | 3) THE SUBMITTED DOCUMENT FOR GAS COOKTOP DOES NOT SHOW | | | THAT THE RANGE OR THE DRYER IS LISTED AND LABELED IN | | | ACCORDANCE WITH 2010 FBC- SEC. G2404.3. | | | 4) SUBMIT MANUF. SPECIFICATIONS FOR THE OPTIONAL GRILL. | | | WPB AMEND. TO FBC SEC. 107.1. | | | 5) THE INSTALLATION MANUALS FOR ALL GAS EQUIPMENT SHALL | | | BE ONSITE FOR THE INSPECTOR PER THE 2010 FBC-RES. SEC. | | | G 2408.1. | | | 6) SUBMIT DETAILS FOR THE VENT FOR THE WATER HEATER IN | | | THE GARAGE. INDICATE VENT TYPE, DIAMETER, ROOF | | | PENETRATION AND HOW IT IS TO BE SEALED AT THE ROOF | | | PENETRATION, ETC. COMPLY WITH 2010 FBC-RES.SECS.G2426 & | | | G2427. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|