| 2015-09-17 07:50:21 | 1ST REVIEW: FBC 2010 MECHANICAL | | | REVISION #15090646 | | | MASTER # 15050778 | | | | | | 1) IN REGARD TO THE NEW RETURN AIR TRANSFER GRILL | | | PLEASE REFER TO SECTION 601.2 FBC-10 MECHANICAL- AIR | | | MOVEMENT IN EGRESS ELEMENTS. | | | CORRIDORS SHALL NOT SERVE AS SUPPLY, RETURN, EXHAUST, | | | RELIEF OR VENTILATION AIR DUCTS. | | | PLEASE REVISE THE RETURN AIR SYSTEM ACCORDINGLY. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|