| Plan Review Notes For Permit 15090611 |
| Permit Number |
15090611 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2016-02-29 10:01:38 | 4TH REVIEW: FBC 2014 MECHANICAL | | | PERMIT #1509-0611 | | | 2/29/16 | | | | | | 1) THE PREVIOUS ENERGY EFFICIENCY FORM WAS MISSING DATA | | | FOR THE RTU AND AC-1. THE REVISED SUBMITTAL IS NOW | | | MISSING COMPLIANCE DATA FOR AC- 2 & 3. PLEASE PROVIDE A | | | COMPLETE SUBMITTAL. | | | 2) M2.1: THE PLAN INDICATES A RETURN GRILL IN THE PAPER | | | MAKING ROOM, HOWEVER NON-RECIRCULATED EXHAUST MAY BE | | | REQUIRED IN THE ROOM PER TABLE 403.3 AND SECTIONS 510 | | | AND 511 IF THE PROCESSES TAKING PLACE THERE PRODUCE | | | FUMES OR DUSTS. PLEASE SUBMIT MANUFACTURER'S | | | SPECIFICATIONS FOR THE PAPER MAKING EQUIPMENT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|