| Date |
Text |
| 2016-02-23 12:26:01 | 4TH ELECTRICAL REVIEW NOTES FOR PERMIT #: 15090611 |
| | |
| | REVIEWED FOR COMPLIANCE WITH: FBC 5TH EDITION 2014 & |
| | NFPA 70 2011 (NEC) |
| | |
| | I FOLLOWED THE SUBMITTED ELECTRICAL RESPONSE LETTER AND |
| | FOUND THAT THE PREVIOUSLY ADDRESSED COMMENTS HAVE BEEN |
| | SATISFIED, BUT BY ADDING THE LIGHTING FOR THE SECOND |
| | FLOOR THE FOLLOWING COMMENTS WERE GENERATED: |
| | 1. THIS ONE COMMENT APPLIES TO THE ENTIRE JOB. |
| | FBC-EC405.2.1.2 HAS LIGHT REDUCTION REQUIREMENTS WHICH |
| | HAVE NOT BEEN ADDRESSED. IN ADDITION TO LIGHT DIMMING, |
| | THERE ARE DAYLIGHT ZONES WHICH SHALL BE TAKEN INTO |
| | ACCOUNT AS WELL.. |
| | 2. YOU ARE INSTALLING CEILING FANS THEREFORE GENERATING |
| | COMPLIANCE WITH NEC 314.27(A),(B), & (C). |
| | 3. DEPENDING ON THE INTENDED WIRING METHOD, NEC |
| | 404.2(C) MAY REQUIRE THAT A GROUNDED CIRCUIT CONDUCTOR |
| | (NEUTRAL) BE PROVIDED AT THE SWITCH LOCATIONS. |
| | 4. THOUGH ALL EXTERIOR OUTLETS ARE MARKED AS WP AND |
| | GFCI NEC 406.9(B) REQUIRES THAT THE RECEPTACLES BE |
| | LISTED ?WEATHER RESISTANT? AS WELL. |
| | 5. IF AHU 1 IS INSIDE AN ATTIC, A LIGHT CONTROLLED VIA |
| | A WALL SWITCH (I SUGGEST IS BE OUTSIDE THE ATTIC IN A |
| | VISIBLE LOCATION AND HAVE A PILOT LIGHT), A SERVICE |
| | OUTLET AND A PERMANENT LADDER TO THE ATTIC WILL BE |
| | REQUIRED. SAME APPLIES FOR AHU 2. |
| | 6. YOU ARE MISSING EMERGENCY LIGHTS IN STORAGE 207 AND |
| | IN STAIRWAYS. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |