| Plan Review Notes For Permit 15090611 |
| Permit Number |
15090611 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-01-11 08:14:18 | 3RD REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15090611 | | | 01/11/16 | | | | | | 1) SHEET M6.1: THE AIR BALANCE SCHEDULE DOES NOT | | | INCLUDE THE MAKE-UP AIR AND EXHAUST CFM'S FOR THE | | | KITCHEN HOOD. | | | 2) M6.1: AN ENERGY RECOVERY VENTILATION SYSTEM IS | | | REQUIRED FOR THE OARTU-1 SERVING THE STUDIO/KITCHEN | | | AREA- SEE TABLE C403.2.6 FBC-14 ENERGY CONSERVATION AND | | | REVISE THE PLANS TO SHOW COMPLIANCE. | | | 3) M2.1: PLACE A DUCT SMOKE DETECTOR SYMBOL IN THE | | | RETURN AIR SYSTEM OF RTU-1 IN ACCORDANCE WITH SECTION | | | 606.2.1 FBC-14 MECHANICAL. | | | 4) THE REVISED ENERGY CALCULATION FORM 506-2014 DOES | | | NOT INCLUDE COMPLIANCE DATA FOR THE RTU'S OR AHU-1. | | | 5) CLARIFY IF EXHAUST SYSTEMS WILL BE PROVIDED FOR ANY | | | OF THE PAPER MAKING EQUIPMENT AND PROVIDE DETAILS ON | | | THE PLAN. | | | 6) M2.1 & M2.2: SHOW ACCESS PANEL LOCATIONS AND | | | DIMENSIONS FOR AHU'S- 1 & 2: SEE SECTION 306.1. | | | 7) M2.3: PLEASE LABEL ON ROOF TOP EQUIPMENT SHOWN ON | | | THE PLAN. | | | 8) PROVIDE A SUBMITTAL FOR THE RTU AND OARTU CURBS | | | REVIEWED AND APPROVED BY THE ENGINEER OF RECORD, AND | | | REVISE SHEET S7.0 TO SHOW DETAILS FOR ATTACHING THE | | | UNITS TO THE CURBS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|