| Date |
Text |
| 2015-11-23 15:52:04 | 2ND REVIEW 2014 MECHANICAL |
| | PERMIT #15090611 |
| | 11/23/15 |
| | |
| | THE MECHANICAL COMMENTS FROM THE 1ST REVIEW STILL |
| | EXIST. NO CORRECTED OR REVISED PLANS HAVE BEEN |
| | SUBMITTED. I HAVE REPRINTED MY COMMENTS FROM THE 1ST |
| | REVIEW BELOW. PLEASE PROVIDE A RESPONSE NARRATIVE |
| | ADDRESSING EACH OF THE COMMENTS, ALONG WITH CORRECTED |
| | PLANS AND SUBMITTALS. |
| | |
| | 1ST REVIEW FBC 2014 MECHANICAL |
| | PERMIT #15090611 |
| | 9/25/15 |
| | |
| | 1) SHEET M6.1: THE O/A CALCULATIONS AND THE AIR BALANCE |
| | SCHEDULE NEED TO BE CORRECTED TO BE IN COMPLIANCE WITH |
| | TABLE 403.3 FBC-14 MECHANICAL: A) OARTU-1 IS SUPPLYING |
| | AIR FOR BOTH THE STUDIO AND THE KITCHEN. BASED ON THE |
| | ARTISTIC RENDITION OF THIS AREA SHOWN ON THE COVER |
| | SHEET OF THE PLANS, THE STUDIO AREA APPEARS TO BE USED |
| | FOR EITHER DOING ART WORK OR VIEWING ART WORK. |
| | THEREFORE, USING TABLE 403.3, PROVIDE CALCULATIONS FOR |
| | EITHER ART STUDIO OR MUSEUMS/GALLERIES. THE KITCHEN |
| | AREA PER TABLE 403.3 MUST BE CALCULATED USING .7 PER |
| | SQ. FT. EXHAUST RATE. IF AIR IS TO BE PROVIDED FOR |
| | KITCHEN OCCUPANTS PLEASE SHOW THAT CALCULATION, AND |
| | RE-CONFIGURE THE PLANS AND AIR BALANCE SCHEDULE PER THE |
| | REVISED CALCULATIONS. PLEASE NOTE THAT THE1190 CFMS FOR |
| | 15 OCCUPANTS SHOWN IN THE SCHEDULE AMOUNTS TO |
| | APPROXIMATELY 80 CFM PER OCCUPANT, HOWEVER YOUR |
| | CALCULATIONS ARE BASED ON 5 CFM PER OCCUPANT. B) REVISE |
| | THE O/A CALCULATIONS IN THE SAME MANNER FOR RTU-1 |
| | SERVING THE GALLERY, AND AHU-1 WHICH IS ALSO SERVING A |
| | GALLERY AREA. |
| | 2) BASED ON THE REVISED O/A CALCULATIONS REFER TO TABLE |
| | C403.2.6 FBC-14 ENERGY CONSERVATION AND REVIEW FOR |
| | APPLICABILITY TO THE PROPOSED OARTU-1 INSTALLATION. |
| | 3) M6.1: PROVIDE AN EQUIPMENT SCHEDULE FOR DHMF-1. |
| | INDICATE HOW THIS UNIT WAS SIZED AND PROVIDE CONTROLS |
| | OPERATION DETAILS. |
| | 4) PROVIDE INSTALLATION DETAILS FOR DHMF-1 AND AHU-1 |
| | 5) DUCT SMOKE DETECTORS ARE REQUIRED TO BE INSTALLED IN |
| | THE RETURN AIR SYSTEMS OF OARTU-1 AND RTU-1. |
| | 6) ENERGY FORM 506-2014: PLEASE ADD THE COMPLIANCE DATA |
| | FOR THE NEW FENESTRATION, AND COMPLETE THE MANDATORY |
| | REQUIREMENTS CHECKLIST BEGINNING ON PAGE 7. |
| | 7) PLEASE PLACE A NOTE ON THE KITCHEN HOOD WILL BE DONE |
| | UNDER A SEPARATE PERMIT AS REQUIRED BY THE WPB |
| | CONSTRUCTION SERVICES DEPT. |
| | 8) SHEET A1.2: SHOW THE LOCATION OF CU-1. |
| | 9) PROVIDE CONDENSATE DISPOSAL PLANS AND DETAILS FOR |
| | THE NEW AC SYSTEMS- SECTION 307. |
| | 10) PROVIDE STRUCTURAL DETAILS FOR THE NEW RTU ROOF |
| | OPENINGS, AND WINDLOAD TIE DOWN ENGINEERING FOR ALL |
| | ROOF TOP HVAC APPLIANCES AND EQUIPMENT- SECTION 301.15 |
| | FBC-4 MECHANICAL. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |