| Date |
Text |
| 2015-10-27 10:41:44 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE2011 EDITION |
| | OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH EDITION |
| | OF THE FBC, (FLORIDA BUILDING CODE) AS APPLICABLE AND |
| | BELOW ARE THE DEFICIENCIES NOTED. |
| | 1. FIXTURE SCHEDULE OR LEGEND SHALL BE REVISED TO MATCH |
| | THE FLOOR PLANS MARKINGS. IT SHALL CLEARLY INDICATE THE |
| | EMERGENCY LIGHTING AS REQUIRED. |
| | 2. ALL LIGHTING SHALL COMPLY WITH THE ENERGY |
| | CONSERVATION REQUIREMENTS FOR THE FBC. |
| | 3. PROVIDE A LIGHTING PLAN FOR THE 2ND FLOOR AREA. |
| | INCLUDE THE STAIRWAY ILLUMINATION AND SWITCHING |
| | REQUIREMENTS. |
| | 4. NEC 210.62 HAS SPECIFIC SHOW WINDOW LIGHTING |
| | REQUIREMENTS NOT ALL OF WHICH HAVE BEEN COMPLIED WITH. |
| | YOU SHALL PROVIDE A SHOW WINDOW OUTLET FOR EVERY 12 |
| | LINEAR FOOT OR PORTION THEREFOF. NOT JUST A SELECTED |
| | SET OF WINDOWS. |
| | 5. NEC 600.5 HAS SPECIFIC REQUIREMENTS FOR SIGN |
| | OUTLETS. IT CALLS FOR A DEDICATED SIGN OUTLET AT EVERY |
| | PEDESTRIAN ENTRY TO EVERY COMMERCIAL ESTABLISHMENT. |
| | THAT DOES NOT MEAN JUST THE FRONT/MAIN DOOR. |
| | 6. PROVIDE A POWER PLAN FOR THE 2ND FLOOR AREA. |
| | 7. SHOW ON THE FLOOR PLAN THE ELECTRICAL OUTLETS OR |
| | POWER SOURCE FOR ALL THE WORK TABLES OR STATIONS. |
| | 8. THE ADDITIONAL OUTLET WILL AFFECT THE ELECTRICAL |
| | LOAD CALCS AND MAYBE THE RISER DIAGRAM. CORRECT THOSE |
| | ACCORDINGLY. |
| | THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN |
| | MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED |
| | FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED |
| | TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG |
| | WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE, |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY |
| | APPRECIATED. |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | |