| Plan Review Notes For Permit 15090603 |
| Permit Number |
15090603 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-09-17 09:45:58 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, | | | FAC9N-3, FBC 1609. A MULLION PRODUCT APPROVAL WAS | | | PROVIDED. A SLIDING GLASS DOOR PROPOSED. | | | | | | 2. PROVIDE INFORMATION REGARDING EXISTING CONDITIONS, | | | FBC 107 (IN THE FORM OF A PLAN) AND PROPOSED. NO | | | INFORMATION REGARDING THE TENANT SPACE HAS BEEN | | | PROPOSED. | | | | | | 3. PROVIDE INFORMATION AS TO HOW THE PROPOSED | | | IMPROVEMENT WILL AFFECT EXITING AND ACCESSIBILITY. SPEC | | | SHEET STATES THAT THE DOOR WILL BE INSTALLED WITHIN A | | | 3/4" RECESS. PROVIDE A PLAN/DETAIL WHICH SHOWS THAT | | | THIS RECESS COMPLIES WITH MEANS OF EGRESS AND | | | ACCESSIBILITY REQUIREMENTS. WON'T THIS CREATE A 3/4" | | | TRENCH? SEE FBC 5TH EDITION ACCESSIBILITY 303. IS THIS | | | AREA RQUIRED TO BE ACCESSIBLE? SHOW COMPLIANCE WITH FBC | | | 1008.1, 1008.1.4.3. NOT ENOUGH INFORMATION PROVIDED TO | | | PERFORM A COMPLETE PLAN REVIEW, FBC 107. | | | | | | |
|