2015-11-17 14:08:42MECHANICAL PROVISO
 REVISION PERMIT #15090594
 MASTER PERMIT #14120130
 11/17/15
  
 1) SHEET M1.3 ROOF PLAN MUST BE REVISED TO SHOW THE
 LOCATIONS OF THE WALK-IN BOX REFRIGERATION CONDENSERS,
 AND THE MINI-PAK UNIT BY COLDZONE (SEE PERMIT
 #15110411).
 2) WIND LOAD ENGINEERING FOR TIE DOWN OF THE ROOFTOP
 CONDENSERS AND FOR THE MINI-PAK UNIT SHALL BE SUBMITTED
 TO THE BUILDING DEPARTMENT PRIOR TO INSPECTION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER