2015-11-14 08:38:23BUILDING PLAN REVIEW
 W. P. B. REVISION: 15090594
 W. P. B. PERMIT: 14120130
 ADD: 1901 S. DIXIE HWY.
 CONT: SISCA
 TEL: (
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SAT.NOV. /2015
  
 ACTION: BUILDING PROVISO
  
  
  
 1) COMPLIED. SHEET A1.2 THE NEW LAYOUT OF FURNATURE AND
 EGRESS PLAN.
  
 2) BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 OF THE PERMITED SET OF DRAWINGS SHEET A4.0 ONLY SHOWS
 THE LOCATION OF THE ROOFTOP RTU UNITS. BOTH S3 & M1.3
 BOTH SHOW A ROOF TOP VEIW OF THE PROJECT THE 3 RTU'S
 AND INTAKE AND ROOF TOP EXHAUST FANS. THERE IS A NOTE
 THE WALKIN CONDENSING UNIT TO BE REMOTE. FINAL LOCATIN
 SHALL BE DETERMINED BY OWNER/ ARCHITECT. REVISION #
 15090594 DOES NOT SHOW A REVISION TO THE ROOF PLAN NOR
 WAS SHEET S3 UPDATED TO SHOW NEW LOCATIONS, SHEET M1.3
 DOES SHOW ON THE MECHANICAL ROOF TOP SHEET A REVISION
 SHOWING THE LOCATION FOR 3 NEWLY LOCATED, (NOT
 HIGHLIGHTED SHOWING A REVISION), ROOF TOP CU UNITS, NO
 DETAILS UNDER MECHANICAL NOR STRUCTURAL SHEETS!!!!!
 PLEASE UPDATE ALL RELEVENT SHEETS TO THE NEW LOCATION
 OF THE 3 NEWLY LOCATED ROOF TOP A/C SPLIT SYSTEMS. WITH
 3 CU SPLIT SYSTEMS IF A ROOF TOP A/C STAND IS TO BE
 INSTALLED. PLEASE PROVIDE THE ATTACHMENT OF THE STAND
 TO THIS SITE SPECIFIC CONDITION. ALSO PROVIDE
 ENGINEERING FOR HOW THE C/U UNIT WILL BE ATTACHED TO
 THE STAND, BY THE ENGINEER OF RECORD.
  
 THE STRUCTURAL ENGINEER HAS NOT INDICATED ON ANY PLANS
 HOW THIS UNIT WILL ATTACH TO THE MWFRS. THE ENGINEER
 HAS PROVIDED (PERMIT SET OF DRAWINGS) DETAILS ON SHEET
 S6 FOR THE ATTACHMENT OF THE RTU'S CURB TO THE MWFRS
 AND THE CLIP SYSTEM FOR MOUNTING THE RTU TO THE CURB.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved