Plan Review Notes
Plan Review Notes For Permit 15090594
Permit Number 15090594
Review Stop E
Sequence Number 1
Notes
Date Text
2015-10-15 18:49:23PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE ELECTRICAL REVIEW OF THE
 ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH
 REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE
 REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED
 SHALL BE RESUBMITTED FOR ANOTHER REVIEW.
 1. IN ADDITION TO THE IN-USE TYPE COVER, THE NEC
 REQUIRES THAT ALL RECEPTACLES IN WET LOCATIONS BE
 LISTED/RATED WEATHER RESISTANT.
 2. APPLICABLE CODES ARE AS FOLLOWS: FFPC-2012, NFPA
 1-2012, NFPA 70 (NEC)-2011, NFPA 72-2010, NFPA 101-2012
 AND FBC 5TH EDITION 2014.
 3. THE QUOTED FBC SECTION HAS NOTHING TO DO WITH THE
 RESPECTIVE NOTE OR COMMENT.
 4. NEC 600.5 REQUIRES THAT THERE BE A DEDICATED SIGN
 OUT ADJACENT TO EVERY PEDESTRIAN ENTRY WAY NOT JUST THE
 MAIN FRONT DOOR. SIGN OUTLET REQ?D BY KANUGA DR. EXIT.
 5. DOOR TO ALLEY WAY IS EXCLUDED FROM THE SIGN OUTLET
 REQUIREMENT.
 6. REVISE THE PANEL SCHEDULES AND SUBSEQUENT LOAD CALCS
 FOR BOTH PANELS A & B.
 7. REVISE THE ELECTRICAL RISER DIAGRAM TO MATCH THE
 PROPOSED SERVICE DISTRIBUTION AND PANEL SCHEDULE.
 8. LOCATION OF LIGHTING CONTROL PANEL DIFFERS BETWEEN
 SHEETS E-1.1 & E-2.1. MAKE THEM MATCH; NEC 210.70(C)
 REQUIRES THAT THERE BE SUFFICIENT ILLUMINATION AT THE
 LOCATION OF ELECTRICAL EQUIPMENT.
 9. BOTH, THE FBC AND THE NEC REQUIRE STAIR ILLUMINATION
 FOR NORMAL AND EMERGENCY CONDITIONS. THEREFORE A LIGHT
 CONTROLLED AT BOTH TOP AND BOTTOM SHALL BE INSTALLED
 FOR THE STAIRWAY AS WELL AS AN EMERGENCY LIGHT
 CONNECTED AHEAD OF ANY SWITCHES ON THE SAME CIRCUIT AS
 THE STAIR LIGHTING.
 10. NEC 314.27(C) REQUIRES THAT CEILING OUTLETS FOR
 PADDLE FANS BE LISTED FOR THE PURPOSE AND CAPABLE OF
 SUPPORTING THE WEIGHT.
 11. BESIDES THE ADDITIONAL LIGHTING REQUIRED FOR THE
 STAIRWAY, MANDATORY LIGHTING CONTROLS ARE REQUIRED FOR
 THE SECOND FLOOR STORAGE AREA.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  