| 2015-10-15 18:49:23 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE ELECTRICAL REVIEW OF THE |
| | ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH |
| | REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE |
| | REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED |
| | SHALL BE RESUBMITTED FOR ANOTHER REVIEW. |
| | 1. IN ADDITION TO THE IN-USE TYPE COVER, THE NEC |
| | REQUIRES THAT ALL RECEPTACLES IN WET LOCATIONS BE |
| | LISTED/RATED WEATHER RESISTANT. |
| | 2. APPLICABLE CODES ARE AS FOLLOWS: FFPC-2012, NFPA |
| | 1-2012, NFPA 70 (NEC)-2011, NFPA 72-2010, NFPA 101-2012 |
| | AND FBC 5TH EDITION 2014. |
| | 3. THE QUOTED FBC SECTION HAS NOTHING TO DO WITH THE |
| | RESPECTIVE NOTE OR COMMENT. |
| | 4. NEC 600.5 REQUIRES THAT THERE BE A DEDICATED SIGN |
| | OUT ADJACENT TO EVERY PEDESTRIAN ENTRY WAY NOT JUST THE |
| | MAIN FRONT DOOR. SIGN OUTLET REQ?D BY KANUGA DR. EXIT. |
| | 5. DOOR TO ALLEY WAY IS EXCLUDED FROM THE SIGN OUTLET |
| | REQUIREMENT. |
| | 6. REVISE THE PANEL SCHEDULES AND SUBSEQUENT LOAD CALCS |
| | FOR BOTH PANELS A & B. |
| | 7. REVISE THE ELECTRICAL RISER DIAGRAM TO MATCH THE |
| | PROPOSED SERVICE DISTRIBUTION AND PANEL SCHEDULE. |
| | 8. LOCATION OF LIGHTING CONTROL PANEL DIFFERS BETWEEN |
| | SHEETS E-1.1 & E-2.1. MAKE THEM MATCH; NEC 210.70(C) |
| | REQUIRES THAT THERE BE SUFFICIENT ILLUMINATION AT THE |
| | LOCATION OF ELECTRICAL EQUIPMENT. |
| | 9. BOTH, THE FBC AND THE NEC REQUIRE STAIR ILLUMINATION |
| | FOR NORMAL AND EMERGENCY CONDITIONS. THEREFORE A LIGHT |
| | CONTROLLED AT BOTH TOP AND BOTTOM SHALL BE INSTALLED |
| | FOR THE STAIRWAY AS WELL AS AN EMERGENCY LIGHT |
| | CONNECTED AHEAD OF ANY SWITCHES ON THE SAME CIRCUIT AS |
| | THE STAIR LIGHTING. |
| | 10. NEC 314.27(C) REQUIRES THAT CEILING OUTLETS FOR |
| | PADDLE FANS BE LISTED FOR THE PURPOSE AND CAPABLE OF |
| | SUPPORTING THE WEIGHT. |
| | 11. BESIDES THE ADDITIONAL LIGHTING REQUIRED FOR THE |
| | STAIRWAY, MANDATORY LIGHTING CONTROLS ARE REQUIRED FOR |
| | THE SECOND FLOOR STORAGE AREA. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU |
| | |