| 2015-10-13 17:55:44 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE ELECTRICAL REVIEW OF THE |
| | ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH |
| | REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE |
| | REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED |
| | SHALL BE RESUBMITTED FOR ANOTHER REVIEW. |
| | 1. NEC 600.5 REQUIRES A DEDICATED SIGN OUTLET ADJACENT |
| | TO EVERY PEDESTRIAN DOOR IN EVERY COMMERCIAL |
| | ESTABLISHMENT. |
| | 2. NEC 210.62 REQUIRES THAT THERE BE A SHOW WINDOW |
| | OUTLET FOR EVERY 12 LINEAR FEET OF SHOW WINDOW |
| | (STOREFRONT) OR PORTION THEREOF. THIS OUTLET SHALL BE |
| | NO MORE THAN 18? ABOVE OR AWAY FROM THE TOP OF THE SHOW |
| | WINDOW. |
| | 3. NEC 422.52 REQUIRES THAT THE ELECTRICAL OUTLET FOR |
| | THE DRINKING FOUNTAIN BE PROTECTED WITH GFCI. |
| | 4. NEC 215.5 REQUIRES A SITE SPECIFIC RISER DIAGRAM |
| | INCLUDING THE TOTAL CALCULATED LOADS BEFORE AND AFTER |
| | AND DEMAND FACTORS. CONDUCTOR SIZING SHALL ALSO BE |
| | INCLUDED. (THIS SHALL INCLUDE EVERY PANELBOARD WITHIN |
| | THE SCOPE OF THIS PERMIT). |
| | 5. NEC 408.4(A) REQUIRES THAT YOU SUBMIT A CIRCUIT |
| | DIRECTORY FOR EVERY PANELBOARD. |
| | 6. NEC 408.4(B) REQUIRES THAT ALL PANELS BE MARKED TO |
| | INDICATE THE LOCATION OF THE SOURCE |
| | 7. FBC-B SECTION 1006 HAS SPECIFIC EMERGENCY LIGHTING |
| | REQUIREMENTS WHICH DO NOT APPEAR TO HAVE BEEN MET. |
| | REVISE YOUR EMERGENCY LIGHTING DETAIL/LAYOUT |
| | ACCORDINGLY. |
| | 8. FBC-E SECTION C405 HAS MANDATORY LIGHTING |
| | REQUIREMENTS FOR COMMERCIAL ESTABLISHMENTS WHICH HAVE |
| | TO BE COMPLIED WITH. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU |
| | |