2015-09-14 17:11:30RESIDENTIAL (R2) FLOORING ALTERATION. BUILDING REVIEW
 COMMENTS.
 CODE: FBC-5TH EDITION (2014).
  
 1- SOUND INSULATION MATERIAL:
 A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED TEST DONE IN ACCORDANCE WITH ASTM E 84 OR UL
 723 AS REQUIRED BY SEC. 720.1 OF FBC 5TH EDITION
 (2014).
  
 B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS
 (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS
 REQUIRED BY SEC. 1207.2 OF FBC 5TH EDITION (2014).
  
 NOTE: TEST SAMPLE TO MATCH ACTUAL BUILDING
 CONSTRUCTION. THICKNESS OF SLAB, SUSPENDED ACOUSTICAL
 CEILING, ETC.
  
 C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS
 (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS
 REQUIRED BY SEC. 1207.3 OF FBC 5TH EDITION (2014).
  
 NOTE: TEST SAMPLE TO MATCH ACTUAL BUILDING
 CONSTRUCTION. FOR EXAMPLE: THICKNESS OF SLAB, SUSPENDED
 ACOUSTICAL CEILINGS (IF INSTALLED), ETC.
  
 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INLCUDE ALL LABOR, MATERIALS AND
 CONTRACTOR'S OVERHEAD AND PROFIT AS REQUIRED BY SEC.
 109.3 CITY AMENDMENTS. SPECIFY ROOM AREAS TO HAVE FLOOR
 TILE INSTALLATION AND TOTAL SQUARE FOOTAGE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]