| Plan Review Notes For Permit 15090549 |
| Permit Number |
15090549 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-09-14 10:35:55 | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PROJECT IS LOCATED IN EXPOSURE CATEGORY D AND | | | THE RAS 117 CALCULATIONS ARE FOR EXPOSURE CATEGORY C. | | | FBC-R 301.2.1.4 | | | | | | 2) THE NUMBER OF INSULATION BOARD FASTENERS (16) | | | SPECIFIED FOR ROOF ZONE 3 EXCEEDS THE NUMBER OF | | | FASTENERS (12) PER BOARD SHOWN IN FIGURE 2 OF RAS 117 | | | FOR FASTENER PLACEMENT FOR 4 FOOT BY 4 FOOT BOARDS. THE | | | ENGINEER SHALL SPECIFY THE FASTENER PLACEMENT WHICH | | | SHALL NOT BE LESS THAN 4" O.C. RAS 117 SECTIONS 8 AND 9 |
|