Plan Review Notes
Plan Review Notes For Permit 15090549
Permit Number 15090549
Review Stop B
Sequence Number 1
Notes
Date Text
2015-09-14 10:35:551ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PROJECT IS LOCATED IN EXPOSURE CATEGORY D AND
 THE RAS 117 CALCULATIONS ARE FOR EXPOSURE CATEGORY C.
 FBC-R 301.2.1.4
  
 2) THE NUMBER OF INSULATION BOARD FASTENERS (16)
 SPECIFIED FOR ROOF ZONE 3 EXCEEDS THE NUMBER OF
 FASTENERS (12) PER BOARD SHOWN IN FIGURE 2 OF RAS 117
 FOR FASTENER PLACEMENT FOR 4 FOOT BY 4 FOOT BOARDS. THE
 ENGINEER SHALL SPECIFY THE FASTENER PLACEMENT WHICH
 SHALL NOT BE LESS THAN 4" O.C. RAS 117 SECTIONS 8 AND 9