2015-12-03 11:37:241) SHT. A-3 - DETAIL #12 - A MINIMUM OF 8 INCHES DEEP
 AT 27 INCHES ABOVE THE FINISH FLOOR IS REQUIRED UNDER
 THE LAVATORY IN ACCORDANCE WITH THE 2014
 FBC-ACCESSIBILITY SEC.306.3.3. ALSO, SEE FIGURE 306.3
 (A).
 2) SHT.P2-1 - THE DRY VACUUM DETAIL SHOWS A 2 INCH CPVC
 VENT FOR THE VACUUM PUMP AND SHT. M-1 CALLS PVC.
 CLARIFY. THE EXHAUST VENT SHALL BE PVC.
 3) SHT. P2-1 - WATER PURIFIER SYSTEM DETAIL SHOWS THE
 DRAIN DIRECTLY CONNECTED TO THE DRAIN. COULD THIS BE A
 POSSIBLE SOURCE OF CONTAMINATION TO THE WATER IF A
 BLOCKAGE OCCURRED IN THE DRAIN TO WHICH IT IS
 CONNECTED? CLARIFY.
 4) SUBMIT MANUFACTURER'S INSTALL MANUAL FOR THE DENTAL
 CHAIRS (2 COPIES). THE RESSPONSE NARRATIVE STATED SPECS
 WERE SUBMITTED BUT THERE WAS NOTHING IN THE SUBMITTAL
 PACKAGE. WPB AMEND. TO FBC SEC. 107.2.1.
 5) SUBMIT A LEGEND FOR ALL THE SYMBOLS USED ON THE
 PIPING DIAGRAMS. WPB AMEND. TO FBC SEC. 107.2.1.
 6) THE VACUUN UNIT DRAIN SHALL BE DIRECTLY CONNECTED TO
 A TRAPPED AND VENTED DRAIN PER 2005 NFPA 99
 SEC.5.3.3.6.3.1.
 7) WHAT ARE THE FUTURE COLD WATER LINES FOR? FUTURE HOT
 WATER LINES MAY BE REQUIRED.
 8) PLEASE STAPLE THE LOOSE PLUMBING SHEETS TO THE REST
 OF THE PLANS.
 9) BACKFLOW PREVENTION DEVICES ARE REQD. ON THE WATER
 SERVICES PER THE CWPB CROSS CONNECTION MANUAL.
  