2015-12-04 12:28:012ND REVIEW 2014 MECHANICAL
 PERMIT #15090433
 12/4/15
  
 1) THE SUBMITTED RESPONSE NARRATIVE TO COMMENT #4 FROM
 THE 1ST REVIEW IS REFERRING TO DETAIL 14 ON SHEET M-2
 FOR WIND LOAD DESIGN FOR TIE DOWN OF THE AC CONDENSERS.
 I HAVE REVIEWED DETAIL 14, AND ALTHOUGH THE DESIGN
 CRITERIA IS NOTED, THE ACTUAL DRAWING DOES NOT INDICATE
 HOW THE STAND IS TO BE ATTACHED TO THE STRUCTURE OR THE
 CONDENSER TO THE STAND. ON SHEET M-2 THERE ARE TWO
 ADDITIONAL TIE-DOWN DETAILS- 9/M-2 AND 10/M-2 WHICH DO
 NOT CORRELATE WITH 14/M-2. PLEASE NOTE THAT YOU HAVE
 ALSO SUBMITTED AND NOA FOR A ROOF STAND. PLEASE PROVIDE
 ONE CLEAR CODE-COMPLIANT METHOD AND REMOVE THE OTHERS
 FROM THE PLANS.
 2) PLEASE PLACE A NOTE INDICATING THE EXHAUST
 TERMINATIONS AT THE REAR OF THE BUILDING WILL BE
 LOCATED MINIMUM 10' ABOVE THE ADJOINING GRADE- SECTION
 501.3.1 ITEM #2 FBC-14 MECHANICAL.
 3) THE RESPONSE NARRATIVE TO COMMENT #7 INDICATES THE
 REQUESTED LOUVER NOA IS ATTACHED TO THE COMMENTS,
 HOWEVER IT HAS NOT BEEN SUBMITTED- PLEASE PROVIDE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER