| Plan Review Notes For Permit 15090433 |
| Permit Number |
15090433 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-12-04 12:28:01 | 2ND REVIEW 2014 MECHANICAL | | | PERMIT #15090433 | | | 12/4/15 | | | | | | 1) THE SUBMITTED RESPONSE NARRATIVE TO COMMENT #4 FROM | | | THE 1ST REVIEW IS REFERRING TO DETAIL 14 ON SHEET M-2 | | | FOR WIND LOAD DESIGN FOR TIE DOWN OF THE AC CONDENSERS. | | | I HAVE REVIEWED DETAIL 14, AND ALTHOUGH THE DESIGN | | | CRITERIA IS NOTED, THE ACTUAL DRAWING DOES NOT INDICATE | | | HOW THE STAND IS TO BE ATTACHED TO THE STRUCTURE OR THE | | | CONDENSER TO THE STAND. ON SHEET M-2 THERE ARE TWO | | | ADDITIONAL TIE-DOWN DETAILS- 9/M-2 AND 10/M-2 WHICH DO | | | NOT CORRELATE WITH 14/M-2. PLEASE NOTE THAT YOU HAVE | | | ALSO SUBMITTED AND NOA FOR A ROOF STAND. PLEASE PROVIDE | | | ONE CLEAR CODE-COMPLIANT METHOD AND REMOVE THE OTHERS | | | FROM THE PLANS. | | | 2) PLEASE PLACE A NOTE INDICATING THE EXHAUST | | | TERMINATIONS AT THE REAR OF THE BUILDING WILL BE | | | LOCATED MINIMUM 10' ABOVE THE ADJOINING GRADE- SECTION | | | 501.3.1 ITEM #2 FBC-14 MECHANICAL. | | | 3) THE RESPONSE NARRATIVE TO COMMENT #7 INDICATES THE | | | REQUESTED LOUVER NOA IS ATTACHED TO THE COMMENTS, | | | HOWEVER IT HAS NOT BEEN SUBMITTED- PLEASE PROVIDE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|