| 2015-10-05 10:06:01 | |
| | 1ST REVIEW: FBC 2014 |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. EXHAUST FROM VACUUM MUST EXTEND TO OUTDOORS SHALL |
| | COMPLY WITH NFPA 99 SEC 5.7.3.6.7.2 |
| | 2. MANUFACTURE SPEC SHEET SHOWS DRAIN DUMPING INTO A |
| | FLOOR SINK, ON SHEET P-3 IT SHOWS A DRAIN STUBBING OUT |
| | OF THE WALL, IT NEEDS TO CHANGE TO A FLOOR SINK OR |
| | PROVIDE MANUFACTURE SPECS SHOWING THE MAXIMUM HEIGHT |
| | THE DRAIN CAN BE CONNECTED. |
| | 3. PLEASE PROVIDE SPECS SHEET FOR PLASTER TRAP AND |
| | DENTAL CHAIRS PER WPB AMEND. 107.2.1 |
| | 4. A SERVICE SINK IS REQUIRED PER FBC P SEC 403.1 |
| | MINIMUM FIXTURES TABLE 403.1 |
| | 5. ON SHEET P-3 SHOW LOCATION OF WATER FILTER ON RISER |
| | DIAGRAM PER WPB AMEND. 107.2.1 |
| | 6. SHEET P-1 SHOW EACH VENT FOR LAVATORY VENTING |
| | THROUGH ROOF , SHEET P-3 SHOWS ALL VENTS TYING TOGETHER |
| | NONE VENTING THROUGH ROOF YOU SHALL HAVE AT LEAST ONE |
| | VENT THROUGH ROOF PER FBC ?P SEC 904.1 ALSO BOTH SHEET |
| | MUST MATCH PER WPB AMEND. 107.2.1 |
| | 7. PLEASE CLARIFY WHERE PAN DRAIN FOR WATER HEATER IS |
| | DRAINING A LAVATORY IS NOT AN APPROVED RECEPTACLE. PER |
| | WPB AMEND. 107.2.1 |
| | 8. |
| | HOT WATER SHALL BE PROVIDED TO SUPPLY ALL OF THE |
| | HOSPITAL FIXTURE, KITCHEN AND LAUNDRY REQUIREMENTS. |
| | SPECIAL FIXTURES AND EQUIPMENT SHALL HAVE HOT WATER |
| | SUPPLIED AT A TEMPERATURE SPECIFIED BY THE |
| | MANUFACTURER. THE HOT WATER SYSTEM SHALL BE INSTALLED |
| | IN ACCORDANCE WITH SECTION 607. PER FBC-P SEC 609.3 IT |
| | APPEARS THAT A 10 GAL. WATER HEATER WILL BE |
| | INSUFFICIENT TO PROVIDE ENOUGH TEMPERED WATER TO 12 |
| | SINKS PLEASE VERIFY. |
| | 9. SHEET P2-1 DETAIL FOR SUCTION LINES DOES NOT MATCH |
| | THE RISER DIAGRAM ON SHEET P-3 PLEASE CLARIFY. PER WPB |
| | AMEND. 107.2.1 |
| | 10. SHEET P-3 SUPPLY RISER DIAGRAM SHOWS EXISTING ? IN. |
| | WATER METER AND MAIN ACCORDING TO TABLE E201.1 IN THE |
| | FBC-P IT MAY BE TOO SMALL; PLEASE PROVIDE CALCULATIONS |
| | TO VERIFY ? IN. WILL BE ADEQUATE SIZE PER WPB AMEND. |
| | 107.2.1 |
| | 11. SHEET A3-2 GRAB BARS SHALL COMPLY WITH FBC ACC SEC |
| | 609.4 |
| | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, |
| | 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) |
| | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF |
| | THE GRIPPING SURFACE, EXCEPT THAT AT WATER CLOSETS FOR |
| | CHILDREN?S USE COMPLYING WITH 604.9, GRAB BARS SHALL BE |
| | INSTALLED IN A HORIZONTAL POSITION 18 INCHES (455 MM) |
| | MINIMUM AND 27 INCHES (685 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE. THE |
| | HEIGHT OF THE LOWER GRAB BAR ON THE BACK WALL OF A |
| | BATHTUB SHALL COMPLY WITH 607.4.1.1 OR 607.4.2.1. |
| | |