Plan Review Notes
Plan Review Notes For Permit 15090433
Permit Number 15090433
Review Stop P
Sequence Number 1
Notes
Date Text
2015-10-05 10:06:01 
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. EXHAUST FROM VACUUM MUST EXTEND TO OUTDOORS SHALL
 COMPLY WITH NFPA 99 SEC 5.7.3.6.7.2
 2. MANUFACTURE SPEC SHEET SHOWS DRAIN DUMPING INTO A
 FLOOR SINK, ON SHEET P-3 IT SHOWS A DRAIN STUBBING OUT
 OF THE WALL, IT NEEDS TO CHANGE TO A FLOOR SINK OR
 PROVIDE MANUFACTURE SPECS SHOWING THE MAXIMUM HEIGHT
 THE DRAIN CAN BE CONNECTED.
 3. PLEASE PROVIDE SPECS SHEET FOR PLASTER TRAP AND
 DENTAL CHAIRS PER WPB AMEND. 107.2.1
 4. A SERVICE SINK IS REQUIRED PER FBC P SEC 403.1
 MINIMUM FIXTURES TABLE 403.1
 5. ON SHEET P-3 SHOW LOCATION OF WATER FILTER ON RISER
 DIAGRAM PER WPB AMEND. 107.2.1
 6. SHEET P-1 SHOW EACH VENT FOR LAVATORY VENTING
 THROUGH ROOF , SHEET P-3 SHOWS ALL VENTS TYING TOGETHER
 NONE VENTING THROUGH ROOF YOU SHALL HAVE AT LEAST ONE
 VENT THROUGH ROOF PER FBC ?P SEC 904.1 ALSO BOTH SHEET
 MUST MATCH PER WPB AMEND. 107.2.1
 7. PLEASE CLARIFY WHERE PAN DRAIN FOR WATER HEATER IS
 DRAINING A LAVATORY IS NOT AN APPROVED RECEPTACLE. PER
 WPB AMEND. 107.2.1
 8.
 HOT WATER SHALL BE PROVIDED TO SUPPLY ALL OF THE
 HOSPITAL FIXTURE, KITCHEN AND LAUNDRY REQUIREMENTS.
 SPECIAL FIXTURES AND EQUIPMENT SHALL HAVE HOT WATER
 SUPPLIED AT A TEMPERATURE SPECIFIED BY THE
 MANUFACTURER. THE HOT WATER SYSTEM SHALL BE INSTALLED
 IN ACCORDANCE WITH SECTION 607. PER FBC-P SEC 609.3 IT
 APPEARS THAT A 10 GAL. WATER HEATER WILL BE
 INSUFFICIENT TO PROVIDE ENOUGH TEMPERED WATER TO 12
 SINKS PLEASE VERIFY.
 9. SHEET P2-1 DETAIL FOR SUCTION LINES DOES NOT MATCH
 THE RISER DIAGRAM ON SHEET P-3 PLEASE CLARIFY. PER WPB
 AMEND. 107.2.1
 10. SHEET P-3 SUPPLY RISER DIAGRAM SHOWS EXISTING ? IN.
 WATER METER AND MAIN ACCORDING TO TABLE E201.1 IN THE
 FBC-P IT MAY BE TOO SMALL; PLEASE PROVIDE CALCULATIONS
 TO VERIFY ? IN. WILL BE ADEQUATE SIZE PER WPB AMEND.
 107.2.1
 11. SHEET A3-2 GRAB BARS SHALL COMPLY WITH FBC ACC SEC
 609.4
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, EXCEPT THAT AT WATER CLOSETS FOR
 CHILDREN?S USE COMPLYING WITH 604.9, GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION 18 INCHES (455 MM)
 MINIMUM AND 27 INCHES (685 MM) MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE. THE
 HEIGHT OF THE LOWER GRAB BAR ON THE BACK WALL OF A
 BATHTUB SHALL COMPLY WITH 607.4.1.1 OR 607.4.2.1.
  