Plan Review Notes
Plan Review Notes For Permit 15090433
Permit Number 15090433
Review Stop M
Sequence Number 1
Notes
Date Text
2015-09-22 14:05:321ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15090433
 9/22/15
  
 1) SHEET M-1 & M-2: DUCT SMOKE DETECTORS WHERE REQUIRED
 SHALL BE INSTALLED IN RETURN AIR SYSTEMS- SEE SECTION
 606.2.1 FBC-14 MECHANICAL.
 2) M-1: REFER TO SECTION 601.2: AIR MOVEMENT IN EGRESS
 ELEMENTS. CORRIDORS SHALL NOT SERVE AS SUPPLY, RETURN,
 EXHAUST, RELIEF OR VENTILATION AIR DUCTS. PLEASE
 PROVIDE DUCTED RETURNS.
 3) THE OUTDOOR AIR AND EXHAUST SYSTEMS SHALL HAVE
 MOTORIZED DAMPERS THAT AUTOMATICALLY SHUT WHEN NOT IN
 USE- REFER TO SECTION C403.2.4.4 FBC-14 ENERGY
 CONSERVATION. SEE ALSO PAGE 10 OF THE SUBMITTED FLORIDA
 ENERGYGAUGE FORM 506-2014 (MANDATORY REQUIREMENTS AS
 APPLICABLE).
 4) M-2: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE CONDENSERS- SEE SECTION 301.15
 FBC-14 MECHANICAL.
 5) M-2: THE DIFFUSER RUN OUT DETAIL 2/M-2 INDICATES
 FLEX DUCT HANGER SPACING OF 6' O.C., HOWEVER 5' O.C
 SPACING IS THE MAXIMUM SPAN PER FIGURE 3-10 SMACNA HVAC
 DUCT CONSTRUCTION STANDARDS- PLEASE CORRECT THE DETAIL.
 6) THE AC SYSTEMS ARE OVERSIZED ACCORDING TO THE
 SUBMITTED CALCULATIONS WHICH INDICATE A COOLING LOAD OF
 24243 BTUH FOR AC-1, AND 32168 FOR AC-2. PLEASE NOTE
 THAT THE AC SCHEDULE ON M-1 DOES NOT LIST COOLING
 CAPACITIES BUT THE TRANE MODEL NUMBERS INDICATE AC-1 IS
 A 36,000 BTU SYSTEM, AND AC-2 IS A 40,000 BTU SYSTEM
 REFER TO SECTION C403.2.2 FBC-14 ENERGY CONSERVATION.
 7) REFER TO PAGE 4 OF ENERGY FORM 506-2014. PLEASE
 CLARIFY WHY THERE IS NO BASELINE VALUE FOR HEAT LISTED
 - THE AC CALCULATIONS INDICATE HEAT LOSS, AND THE
 SCHEDULES INDICATES 5KW HEATERS TO BE INSTALLED.
 8) PROVIDE TWO COPIES OF FL. PRODUCT APPROVALS OR
 MIAMI-DADE NOA'S FOR THE EXHAUST AND AIR INTAKE
 LOUVERS- DEPT. OF COMMUNITY AFFAIRS & FAC RULE 9N-3.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  