2015-09-29 08:18:10BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15090433
 ADD: 1987 PALM BEACH LAKES
 CONT: DOUGLAS M. PISARSKI, INC.
 TEL: (561)662-3818
 E-MAIL:[email protected]
  
 2014 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. SEPT. 29/2015
 ACTION: DENIED
  
 1) SHEET A1 AND A4.1 DETAIL # 6 SHOWS A RE-CONFIGURED
 EXTERIOR DOOR OPENING. THE DETAIL SHOWS A NEW LINTEL
 AND DETAILING HOW TO ANCHOR THE NEW # 5 REBAR TO THE
 FOUNDATION BUT THERE IS NO INFORMATION AS TO HOW THE
 REBAR IS TO BE ATTACHED TO THE BEAM ABOVE. NOTE THE
 FILLED CELLS AND REBAR AREPART OF THE MAINWIND FORCE
 RESISTING SYSTEM. PLEASE PROVIDE ADDITIONAL
 INFORMATION. 107.2.1.3.
  
 2) SHEET FP-1 INDICATES 2 MEANS OF EGRESS ARE REQUIRED
 AND 2 MEANS OF EGRESS ARE PROVIDED. NOTE THE 2014 FBC-B
 TABLE 1014.3 COMMON PATH OF TRAVEL FOR A
 NON-SPRINKLERED BUSINESS OCCUPANCY WITH A OCCUPANT LOAD
 OF 30 OR LESS THE COMMON PATH OF TRAVEL IS 100 FT. FROM
 THE FURTHEST POINT IN THE TENANT SPACE IT IS ONLY 70
 FEET. THE 2ND MEANS OF EGRESS IS THROUGH TREATMENT ROOM
 NUMBER 3. THE MINIMUM CLEAR EGRESS WIDTH IS 36 INCHES
 SEE TABLE 1018.2. IT APPEARS THERE IS 36 INCHES FROM
 THE PATIENT CHAIR TO THE WALL BUT THERE MAYBE AN
 OBSTRUCTION WITH AN X-RAY MACHINE HUNG FROM THE WALL.
 2014 FBC-B 1005 MEANS OF EGRESS SIZING SECTION 1005.7.3
 PROTRUDING OBJECTS SHALL COMPLY WITH APPLICABLE
 REQUIREMENTS OF SECTION 1003.3.
 1003.3.3 HORIZONTAL PROJECTIONS. STRUCTURAL ELEMENTS,
 FIXTURES, OR FURNISHINGS SHALL NOT PROJECT HORIZONTALLY
 FROM EITHER SIDE MORE THAN 4 INCHES OVER ANY WALKING
 SURFACE BETWEEN 27 INCHES AND 80 INCHES ABOVE THE
 WALKING SURFACE.
  
 3) THE SUBMITTED WINDOW PRODUCT APPROVAL A MIAMI-DADE
 NOA ES WINDOWS NOA # 14-0923.09 IS SMALL MISSILE TESTED
 AND WILL REQUIRE STORM SHUTTERS. 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(E) SHUTTERS
  
 4) PLEASE PROVIDE THE ADDITIONAL INFORMATION WITH THE
 STORM SHUTTER PRODUCT APPRROVAL. STORM SHUTTERS PROVIDE
 STORM PANEL INFORMATION WITH INSTALLATION SCHEDULE AND
 KEY PLAN WITH SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING. FBC 1609.1.2.
  
 FL BLD CODE 2010 SECTION 107.2.1.3,1609.1.2, 1715.8 &
 EXIST BUILD CODE 606.4 PROCEDURES: A COMPLETE
 INSTALLATION SCHEDULE SUMMARIZING & IDENTIFYING OPENING
 SIZES, STORY HEIGHTS, UNIT MARK NUMBERS, UNIT
 SPANS/WIDTHS, UNIT STORM BAR REINFORCING REQUIREMENTS,
 WALL PRESSURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION TO FACILITATE
 PLAN REVIEW AND PERMIT ISSUANCE.
  
 5) THE ABOVE STATE WINDOW NOA 14-0923.09 DOES NOT
 INCLUDE ANY MULLION INFORMATION WITHIN THE DOCUMENT
 WINDOW TYPES A, B, AND C WILL REQUIRE A MULLION TO JOIN
 THE THE TOGETHER. 2014 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(B) WINDOWS, MULLIONS
  
 6) SHEET A4-1 THE DOR SCHEDULE INDICATES DOOR
 IDENTIFIED AS E3 REQUIRING NOA 12-0223.32 NOT SUBMITTED
 WITH THIS REVIEW. 2014 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 7) SHEET A-4.1 INDICATES THE ULTIMATE WIND SPEED AS 170
 VULT AND EQUAL TO 130 VASD. PLEASE NOTE THE THE 170
 VULT IS EQUAL TO 132 VASD. PLEASE UPDATE CORRECTIONS.
 SEE 2014 FBC-B TABLE 1609.3.1 WIND SPEED CONVERSION.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676