| Plan Review Notes For Permit 15090428 |
| Permit Number |
15090428 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-09-22 07:01:46 | | | | 1ST REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | | | | PLUMBING COMMENTS: | | | | | | 1. SHEET P1 PLUMBING RISER IS NOT SIZED COMPLETELY OR | | | PER CODE SHALL BE SIZED TO COMPLY WITH. FBCP SEC 710.1 | | | MAXIMUM FIXTURE UNIT LOAD.AND TABLE 710.1(1) BUILDING | | | DRAINS AND SEWERS. | | | 2. WASHING MACHINE SHALL BE SHOWN ON RISER AND FLOOR | | | PLAN ON SHEET P3 . PER WPB AMEND. SEC 107.2.1 | | | 3. PLEASE PROVIDE WATER RISER. PER.WPB AMEND. | | | SEC107.3.5.3(11) |
|