Plan Review Notes
Plan Review Notes For Permit 15090428
Permit Number 15090428
Review Stop E
Sequence Number 1
Notes
Date Text
2015-10-20 16:48:361ST REVIEW: FBC 2014 5TH ED.
  
 PLEASE MODIFY THE PLAN TO INDICATE COMPLIANCE WITH THE
 FOLLOWING SECTIONS:
  
 FBCRE3902.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE,
 15- AND 20-AMPERE OUTLETS INSTALLED IN FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUNROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE PROTECTED
 BY A COMBINATION TYPE ARC-FAULT CIRCUIT INTERRUPTER
 INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT.
  
 E3703.2 KITCHEN AND DINING AREA RECEPTACLES.
 A MINIMUM OF TWO 20-AMPERE-RATED BRANCH CIRCUITS SHALL
 BE PROVIDED TO SERVE ALL WALL AND FLOOR RECEPTACLE
 OUTLETS LOCATED IN THE KITCHEN, PANTRY, BREAKFAST AREA,
 DINING AREA OR SIMILAR AREA OF A DWELLING. THE KITCHEN
 COUNTERTOP RECEPTACLES SHALL BE SERVED BY A MINIMUM OF
 TWO 20-AMPERE-RATED BRANCH CIRCUITS, EITHER OR BOTH OF
 WHICH SHALL ALSO BE PERMITTED TO SUPPLY OTHER
 RECEPTACLE OUTLETS IN THE SAME KITCHEN, PANTRY,
 BREAKFAST AND DINING AREA INCLUDING RECEPTACLE OUTLETS
 FOR REFRIGERATION APPLIANCES.
  
 FBCRE4002.14 TAMPER-RESISTANT RECEPTACLES.
 IN AREAS SPECIFIED IN SECTION E3901.1, 125-VOLT, 15-
 AND 20-AMPERE RECEPTACLES SHALL BE LISTED
 TAMPER-RESISTANT RECEPTACLES.
  
 FBC-R 315.1 ? CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH SLEEPING ROOM.
  
 FBC- 107.3.5.3 ? SMOKE DETECTORS PURSUANT TO FBC-R
 314.3.1 AS REQUIRED FOR NEW DWELLINGS
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  