| Plan Review Notes For Permit 15090428 |
| Permit Number |
15090428 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-10-20 16:16:39 | 1ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL & EXISTING | | | BUILDING VOLUMES | | | | | | THE CODE IN EFFECT LISTED IN THE CODE SUMMARY ON SHEET | | | A1.0 IS OUT DATED, SEE ABOVE FOR CURRENT VERSION. | | | | | | THE PLAN INDICATES ROOFING WINDOWS AND DOORS WILL BE | | | REPLACED. | | | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR | | | SUBMITTALS. | | | | | | ALTHOUGH THE PLAN NOTES INDICATE AN ENERGY SUBMITTAL | | | WILL BE PROVIDED, THE HOME IS EXEMPT FROM THE | | | REQUIREMENT AS IT IS CONSIDERED A CONTRIBUTING HISTORIC | | | STRUCTURE. EITHER PROVIDE A SUBMITTAL OR REMOVE THE | | | NOTES FROM THE PLAN. | | | | | | FBC-R 315.1 PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 | | | FEET OF EACH SLEEPING ROOM. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|