| 2015-09-24 11:58:21 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15090419 |
| | ADD: 700 S. ROSEMARY AVE. SUITE # 208 |
| | CONT: JOHN A. DURANICO |
| | TEL: (561)683-9972 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. SEPT. 24/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-1 SHOWS A NEW ACCESSIBLE STALL IN THE LADIES |
| | RESTROOM. THE BACK WALL IS NOT DIMENSIONED, BUT THE |
| | WALLS ACROSS FORM THE STALL LINE UP AND THE 5FT. 4 |
| | INCHES AND 1 FT. 7 1/2 INCHES ADD UP TO EQUAL 6 FT. 9 |
| | 1/2 INCHES. THE MINIMUM LENGTH OF THE BACK WALL IS 7 |
| | FT. 1 INCH WITH THE LAV BEING SET AT 15 INCHES FORM THE |
| | WALL AND A WIDTH OF 19 INCHES. 2014 FBC-ACCESSIBILITY |
| | CODE 604.3.2 & 604.8.1. |
| | |
| | 2) THE DOOR SHOULD BE NO FURTHER AWAY FROM THE CORNER |
| | OF THE TOILIET COMPARTMENT THAN 4 INCHES. 2014 |
| | FBC-ACCESSIBLITY CODE 604.8.1.2. |
| | |
| | 3) THE DOOR TO THE ACCESSIBLE STALL IS NOT DIMENSIONED, |
| | PLEASE SHOW COMPLIANCE WITH 2014 FBC-ACCESSIBLITY CODE |
| | 404.2.3. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |