| Plan Review Notes For Permit 15090402 |
| Permit Number |
15090402 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-01-27 13:14:50 | 1) THE RESPONSE FROM THE ENGINEERING FIRM FOR THE GAS | | | COMMENT REGARDING COMBUSTION AIR REFERS TO SHT. M301. | | | THERE IS NO SUCH DRAWING IN THIS SET OF PLANS. CLARIFY. | | | 2) SHT. M401 - WATER HEATER COMBUSTION AIR CALCULATIONS | | | SHOWS THE TANKLESS WATER HEATER AS 35,000 BTU'S AND THE | | | GAS RISER SHOWS THE BTU LOAD AS 199,000 BTU'S. THIS IS | | | OBVIOUSLY A MISPRINT. REVISE. | | | 3) THE PLUMBING PLANS SHALL BEAR THE WET SIGNATURE OF | | | THE ENGINEER OF RECORD PER THE F.A.C. RULE | | | 61G15-23.001, .002, & .003. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|