| 2016-03-29 10:16:00 | 4TH ELECTRICAL REVIEW NOTES FOR PERMIT 15090401 . PLANS |
| | FILED UNDER PERMIT #:15090395 |
| | REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014, |
| | NFPA 70 2011 (NEC) |
| | |
| | CORRECTIONS REQUIRED: |
| | |
| | 1. PER A TELEPHONE CONVERSATION WITH ANDREW OF |
| | SILBERSTEIN ARCHITECTURE THE SOUTH ELEVATION OF UNIT |
| | ?B? WILL BE REVISED TO SHOW THE SLIDING DOOR ENTRY FROM |
| | THE COURTYARD. IN DOING SO, THE RECEPTACLES NOW |
| | INDICATED ON THE PLANS SHALL BE RELOCATED TO MEET NEC |
| | 210.52 REQUIREMENTS. |
| | 2. THE ADDITION OF THE DOOR/ENTRY WILL GENERATE THE |
| | NEED TO LIGHT CONTROL AS PER NEC 210.70 FOR THE |
| | REQUIRED LIGHT OUTSIDE THE DOOR. |
| | 3. NEC 210.52 (E)(3) REQUIRES THAT YOU PROVIDE A GFI |
| | OUTLET IN EVERY BALCONY GREATER THAN 20 SQ. FT. (B202, |
| | B302 & B306) |
| | 4. IN THE INTEREST OF LIFE SAFETY, USER CONVENIENCE AND |
| | ENERGY CONSERVATION, 3 WAY SWITCHING IS RECOMMENDED AT |
| | A MINIMUM FOR THE TRAVERSE LIGHTING. |
| | 5. FBC-R MECHANICAL VENTILATION IS REQUIRED FOR ROOMS |
| | B102, B303 & B304. THE EXHAUST FAN SHALL COME ON WITH |
| | THE LIGHT. |
| | 6. NEC 314.27 A LISTED FAN BOX IS REQUIRED FOR ROOM |
| | B101. |
| | 7. NEC 210.70 REQUIRES THAT ROOM LIGHTS BE SWITCH UPON |
| | ENTRY, THEREFORE IF WALL CONTROL IS DESIRED FOR THE |
| | PADDLE FAN, AN ADDITIONAL SWITCH WILL BE REQUIRED. |
| | 8. NEC 404.2(C) REQUIRES THAT A GROUNDED CONDUCTOR BE |
| | PROVIDED AT EVERY LIGHT SWITCH. |
| | 9. FBC-ER404.1 REQUIRES THAT A MINIMUM OF 75% OF THE |
| | LAMPS IN PERMANENTLY INSTALLED FIXTURES BE HIGH |
| | EFFICIENCY. |
| | 10. THESE COMMENTS ARE IN ADDITION TO ANY OF THE |
| | PREVIOUSLY MENTIONED WHICH HAVE NOT YET BEEN SATISFIED. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |