| Plan Review Notes For Permit 15090394 |
| Permit Number |
15090394 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2016-03-30 11:34:33 | APPROVED WITH PROVISOS AS MENTIONED BELOW: | | | I REVIEWED THE NEWLY SUBMITTED SHEETS YESTERDAY AND | | | FOUND A FEW MINOR ISSUES THAT I BELIEVE CAN BE | | | ADDRESSED WITH A PROVISO AS LONG AS THE DESIGN | | | PROFESSIONAL AGREES WITH THESE ITEMS. THEY ARE AS | | | MENTIONED BELOW: | | | | | | 1. SHEET E101: FIRE ALARM NOTES 2 QUOTES THE 2008 | | | EDITION OF THE NEC WHEN IN FACT THE APPLICABLE CODE | | | WOULD BE THE 2011 EDITION. CORRECT ACCORDINGLY. | | | 2. INITIALLY WE HAD DISCUSSED THAT THE HOUSE METER AND | | | PANEL WOULD BE ON THE BLDG. A WALL, THE PLAN CALL FOR A | | | UNI-STRUT STRUCTURE TO SUPPORT THESE ITEMS. IF THIS IS | | | FACT WHAT IS PLANNED, PLEASE MAKE CERTAIN THAT ALL | | | SHARP EDGES OF THE UNI-STRUT BE PROTECTED WITH END CAPS | | | AND THAT THERE BE PROTECTION FROM PHYSICAL DAMAGE IF | | | REQUIRED. | | | 3. SHEET E102: THOUGH THE END RESULT WILL NOT VARY, THE | | | ELECTRICAL LOAD CALCS DO NOT APPEAR TO BE CORRECT. | | | 4. SHEET E201: REMINDER THAT THE REQUIRED UTILITY | | | EASEMENTS SHALL BE FILES BEFORE ANY FINALS CAN BE | | | SECURED. | | | 5. NEC 300.5(D)(3) REQUIRES THAT THERE BE A CAUTION | | | RIBBON PLACED IN THE SERVICE TRENCH 12"ABOVE THE | | | RACEWAYS. | | | | | | THANK YOU, | | | MIKE ALBARRAN | | | ELECTRICAL PLANS EXAMINER | | | PH: 561-805-6746 | | | EMAIL: [email protected] |
|