| Plan Review Notes For Permit 15090394 |
| Permit Number |
15090394 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-12-01 14:48:10 | 2ND REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | | | | | | | GAS COMMENTS | | | | | | 1.MEP SHEETS DO NOT COMPLY WITH FL ADMEN CODE | | | SE61G15-23.003 PROCEDURES FOR PHYSICALLY SIGNING AND | | | SEALING PLANS, SPECIFICATIONS, REPORTS OR OTHER | | | DOCUMENTS. | | | ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER | | | DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN | | | ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025, | | | F.S., AND RULE 61G15-23.001, F.A.C. MAY BE PHYSICALLY | | | SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE | | | PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. | | | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE | | | LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE | | | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR | | | COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE | | | USED. | | | (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY | | | CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY | | | OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE | | | REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL | | | NOT RENDER THE SIGNATURE ILLEGIBLE. | | | | | | | | | 2.PLEASE PROVIDE DETAIL AND MANUFACTURE INSTALLATION | | | GUIDE FOR WATER HEATER VENT. PER WPB AMEND TO FBC SEC | | | 107.2.1 SHEET M401 IS REFERENCED IN YOUR RESPONSE BUT | | | IT IS NOT INCLUDED IN THE PLAN SET. |
|