| 2015-12-22 17:33:49 | DECEMBER 22ND, 2015 2ND. ELECTRICAL REVIEW |
| | |
| | RE: RESPONSE TO FIRST REVIEW COMMENTS FOR THE PARK |
| | SLOPE TOWNHOUSES. |
| | |
| | BELOW IS MY RESPONSE TO YOUR COMMENTS. PLEASE NOTE THAT |
| | THEY APPEAR IN THE SAME ORDER IN WHICH YOU SUBMITTED |
| | THEM TO ME. |
| | |
| | 10) I INFORMED YOU THAT WE WILL NEED A COPY OF THE |
| | RECORDED EASEMENTS BEFORE WE CAN APPROVE THE ELECTRICAL |
| | REVIEW. YOU DELEGATED TO SOMEONE ELSE, BUT REGARDLESS |
| | OF WHO SECURES THE EASEMENTS. A COPY OF THE RECORDED |
| | DOCUMENTS SHALL ACCOMPANY YOUR SUBMITTAL PRIOR TO |
| | APPROVAL. |
| | |
| | 11) WE ALREADY ESTABLISHED A SEPARATE PERMIT FOR THE |
| | HOUSE METER AND OTHER ITEMS RELATED THERETO. |
| | |
| | 12) WE CONCUR ON THE POOL PERMIT ISSUE. |
| | |
| | 13) YOU CORRECTED THE NOTE BUT INCORRECT CODE |
| | REFERENCES REMAIN. THE PROPER CODES TO FOLLOW ARE: THE |
| | FLORIDA FIRE PREVENTION CODE (FFPC) 2012, NFPA 70 |
| | (NATIONAL ELECTRICAL CODE) 2011, NFPA 72 2010 EDITION, |
| | AND THE 5TH EDITION OF THE 2014 FLORIDA BUILDING CODE |
| | (FBC). CORRECT YOUR NOTE ACCORDINGLY. |
| | |
| | 17) YOU CONTINUE TO REFER TO A NONEXISTENT CABLE. BX |
| | CABLE IS NOT RECOGNIZED IN THE CODE BOOK. |
| | |
| | 30 - 35) REFER TO SHEET E401 & E402 WHICH WAS NOT |
| | PROVIDED. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME. HAVE A VERY MERRY CHRISTMAS AND A |
| | PROSPEROUS 2016. |
| | |
| | MIKE ALBARRAN, |
| | ELECTRICAL PLANS EXAMINER |