| Plan Review Notes For Permit 15090394 |
| Permit Number |
15090394 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-09-21 06:58:05 | 1ST REVIEW: FBC 2014 | | | | | | GAS COMMENTS: | | | 1.SHEETS P203 AND P303 YOU REFERENCED SIZING TABLES | | | FROM FBC FUEL GAS 2010 AND ON P303 THE TABLE ON THE LOW | | | PRESSURE SIDE OF THE RISER IS NOTE MATCHING UP TO THE | | | TABLE AT THE TOP OF THE PAGE . THE RISER APPEARS TO BE | | | OVER SIZED PLEASE RESIZE USE TABLES FROM FBC FUEL GAS | | | 2014. | | | 2. PLEASE PROVIDE COMBUSTION AIR CALCULATIONS FOR WATER | | | HEATER AND DRYER. PER WPB AMEND 107.2.1 | | | 3. PLEASE PROVIDE SPEC SHEETS ON DRYER, TANKLESS HEATER | | | AND RANGE. PER WPB AMEND 107.2.1 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|