| 2015-09-11 18:11:34 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR |
| | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED |
| | ORIGINALS, FS 471. POOR QUALITY PHOTOCOPIES WERE |
| | SUBMITTED. |
| | |
| | 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR |
| | THE SOLAR VENT. PROVIDE THE COVER SHEET WHICH SHOWS THE |
| | APPROVAL NUMBER, CODE VERSION, AND STATUS |
| | (WWW.FLORIDABUILDING.ORG). IT APPEARS THAT THE |
| | EVALUATION REPORT PROVIDED IS EXPIRED AS IT MAKES |
| | REFERENCE TO FBC 2010 (GOVERNING CODE IS FBC 5TH |
| | EDITION, AKA FBC 2014). |
| | |
| | 3. SEE INSTALLATION NOTES, ITEM 7.3, "PRODUCT SHALL BE |
| | INSTALLED ON ROOFS UTILIZING ASPHALT SHINGLES ONLY". |
| | |
| | 4. REVISE ROOF PLAN TO SHOW THE LOCATION OF PROPOSED |
| | ROOF VENT AND ROOF SHEATHING INFORMATION (TYPE OF ROOF |
| | SHEATHING, THICKNESS). THIS INFORMATION IS REQUIRED DUE |
| | TO LIMITATIONS FOR THE ROOF VENT. |
| | |
| | 5. PURPOSE OF PROPOSED VENT IS NOT CLEAR. FLAT DECK |
| | ROOFS TYPICALLY DO NOT HAVE AN ATTIC SPACE. WHAT IS |
| | BEING VENTED? |
| | |
| | 6. CONTRACTOR TO CONFIRM THAT A FIRE BARRIER IS |
| | PROPOSED. CONTRACTOR HAS SELECTED THE ASSEMBLY ON PAGE |
| | 12 OF 13, NOA 12-1019.34, SYSTEM TYPE E. NOTE THAT THE |
| | SYSTEM PROPOSED INCLUDES A FIRE BARRIER. THIS IS NOT |
| | OPTIONAL. OPTIONAL ITEMS WILL STATE (OPTIONAL); FOR AN |
| | EXAMPLE OF AN OPTIONAL COMPONENT, SEE PAGE 9, VAPOR |
| | RETARDER. SINCE THE FIRE BARRIER IS NOT "OPTIONAL" IT |
| | IS A PART OF THIS ASSEMBLY AND IS REQUIRED. |
| | |
| | |
| | |
| | |
| | |
| | |