| Plan Review Notes For Permit 15090327 |
| Permit Number |
15090327 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2016-07-08 14:55:57 | RESIDENTIAL (R3) ALTERATION FOURTH BUILDING REVIEW | | | CHECKLIST. | | | CODE: 2014 FBC 5TH EDITION (2014). | | | | | | ORIGINAL COMMENT: | | | 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. | | | R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION | | | (2014). | | | NOTE: PLANS AND ENERGY CALCULATIONS TO BE COORDINATED | | | TO AVOID CONFLICTS OR DELAYS. | | | RESPONSE: TALKED TO MECHANICAL ENGINEER (RYAN TODARO) | | | WHO PREPARED THE ENERGY CALCULATIONS SUBMITTED. ENERGY | | | CALCULATIONS SUBMITTED IS FOR A COMMERCIAL PROJECT. | | | NEED TO USE RESIDENTIAL FORM R402 FOR PRESCRIPTIVE | | | METHOD OR R405 FOR PERFORMANCE METHOD. | | | PERMIT CAN NOT BE ISSUED WITHOUT THE ENERGY | | | CALCULATIONS. SEE SEC. R103.1.1.2 FBC-ENERGY | | | CONSERVATION, 5TH EDITION (2014). | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|