| 2015-10-27 17:31:58 | RESIDENTIAL (R3) ALTERATION/CONVERSION BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2014 FBC 5TH EDITION (2014). |
| | |
| | 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) |
| | FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED |
| | PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY |
| | IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT |
| | CODE. |
| | |
| | 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | NOTE: PLANS AND ENERGY CALCULATIONS TO BE COORDINATED |
| | TO AVOID CONFLICTS OR DELAYS. |
| | |
| | 3- SIZES OF WINDOWS SHOWN ON THE FLOOR PLAN ON SHEET |
| | A.2 DON'T MATCH SIZES SHOWN ON THE EXTERIOR ELEVATIONS. |
| | WINDOWS SHOWN ON THE EXTERIOR ELEVATIONS DON'T COMPLY |
| | WITH EGRESS. PROVIDE CLEAR INFORMATION FOR THE EGRESS |
| | WINDOW OF THE NEW BEDROOM SHOWING COMPLIANCE WITH ALL |
| | THE REQUIREMENTS OF SEC. R310 OF FBC-RESIDENTIAL, 5TH |
| | EDITION (2014). |
| | |
| | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) STORM SHUTTERS. AND, PROVIDE COMPLETE INSTALLATION. |
| | SEE CITY SAMPLE FOR SHUTTERS INSTALLATION SCHEDULE. |
| | NOTE: SHUTTERS REQUIRED BECAUSE WINDOWS PRODUCT |
| | APPROVAL SUBMITTED IS FOR NON-IMPACT WINDOWS. |
| | |
| | B) WINDOW MULLIONS. AND, CLEARLY MARK SIZE TO BE |
| | INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). |
| | NOTE: PROVIDE 2 COPIES. ONLY ONE COPY WAS SUBMITTED |
| | THIS TIME. AND PROVIDE COMPLETE DRAWINGS. NOA |
| | 11-1213.07 SUBMITTED IS MISSING SHEETS 4 OF 6 TO 6 OF |
| | 6. |
| | |
| | C) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | |
| | 5- DESIGNER OF RECORD TO APPROVE IN WRITING (NOT |
| | SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED |
| | BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE |
| | OLD/VOID DRAWINGS TO RESUBMITTED SET OF DRAWINGS. |
| | SUBMIT OLD/VOID DRAWINGS FOR REFERENCE. |
| | |