Plan Review Notes
Plan Review Notes For Permit 15090321
Permit Number 15090321
Review Stop B
Sequence Number 1
Notes
Date Text
2015-09-15 10:09:09PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE MAXIMUM DESIGN PRESSURE FOR THE FASTENING OPTION
 THAT YOU INDICATED ON PAGE 25 OF NOA NO. 14-0611.01 IS
 -45 PSF WHICH IS NOT ADEQUATE FOR THE PERIMETER AND
 CORNER ROOF ZONES OF A TWO STORY STRUCTURE LOCATED IN A
 170 MPH VULT. WIND SPEED. SUBMIT TWO SETS OF SIGNED AND
 SEALED RAS 117 CALCULATIONS AS REQUIRED BY LIMITATION
 #7 ON PAGE 29 OF THE PRODUCT APPROVAL.