| Plan Review Notes For Permit 15090268 |
| Permit Number |
15090268 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-11-03 10:12:31 | PLEASE INDICATE IF LOCATION OF TRANSFORMER CHANGES AND | | | CONFIRM CLEARANCE REQUIREMENTS ALONG WITH ATTACHMENT TO | | | THE BUILDING GROUNDING ELECTRODE SYSTEM AND BONDING OF | | | OTHER SYSTEMS. | | | PROVIDE SUPPORT OR HANGING INFORMATION FOR TRANSFORMER, | | | IF EXISTING, PLEASE SO INDICATE AND IDENTIFY POINT LOAD | | | CONFORMANCE ON STRUCTURE | | | GROUNDING RECEPTACLE DETAIL DOES NOT INDICATE THE IF | | | UNGROUNDED OR GROUNDED CONDUCTOR "FEEDS THRU" THE | | | RECEPTACLE, 2 OF 3 CONDUCTORS ARE SPLICED AND TAILED. | | | EXISTING SYMBOL IN OFFICE 1136 SHOWN AT 5'8" DOES NOT | | | APPEAR IN THE LEGEND. PLEASE DEFINE (CATV?) | | | REFERENCED DOCUMENTS UNDER ELECTRICAL NOTE 1 DO NOT | | | CORRESPOND TO THE FLORIDA BUILDING CODE CHAPTER 35 | | | ELECTRICAL NOTE #27 INDICATES A NON-STANDARD BOX, | | | PLEASE PROVIDE LISTING INFORMATION | | | ELECTRICAL NOTE #23 REQUIRES "CLEANING" OF ALL DEVICES | | | AND EQUIPMENT. ENSURE ITEMS ARE NOT DAMAGED AND COMPLY | | | WITH NEC 110.11 | | | | | | REVIEW PERFORMED BY: | | | DOUG HARVEY | | | [email protected] | | | 561-805-6740 |
|