Plan Review Notes
Plan Review Notes For Permit 15090205
Permit Number 15090205
Review Stop M
Sequence Number 2
Notes
Date Text
2015-11-06 08:03:592ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15090205
 11/6/2015
  
 1) THE HEAT PUMP SCHEDULE ON SHEET M1.1 INDICATES
 OVERSIZING OF COOLING CAPACITY FOR RTU #6, WHEN
 COMPARED WITH THE CALCULATIONS ON SHEET M1.5- REFER TO
 SECTION C403.2.2 FBC-14 ENERGY CONSERVATION.
 2) THE EFFICIENCY RATINGS OF THE NEW HEAT PUMPS (11.8
 EER FOR RTU'S 2-6, AND 13 SEER FOR RTU-1) AS LISTED IN
 THE RE-SUBMITTED ENERGY CALCS DO NOT MATCH THE RATINGS
 LISTED IN THE SCHEDULE- (10.6 & 11.2 EER). A) THE
 REQUIRED INPUT DATA REPORT WAS NOT SUBMITTED WITH THE
 REVISED CALCULATION FORM 506-2014, AND THE MANDATORY
 REQUIREMENTS CHECKLIST WAS NOT CHECKED OFF.
 B) PLEASE NOTE THAT DUPLICATE COPIES OF THE ENERGY CODE
 SUBMITTALS ARE REQUIRED- ONLY ONE FORM WAS SUBMITTED.
 3) SHEET M1.2, ROOFTOP UNIT DETAIL: PLEASE SHOW A DUCT
 SMOKE DETECTOR IN THE RETURN PLENUM OF THE RTU- SECTION
 606.2.1 FBC-14 MECHANICAL.
 4) COMMENT #10 FROM THE 1ST REVIEW REGARDING PERMIT
 VALUATION STILL EXISTS: PLEASE COMPLY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  