| 2015-10-14 10:00:39 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE ELECTRICAL REVIEW OF THE |
| | ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH |
| | REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE |
| | REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED |
| | SHALL BE RESUBMITTED FOR ANOTHER REVIEW. |
| | 1. FOR THE FUTURE, I DON?T KNOW IF YOU ARE AWARE OF A |
| | CITY OF WEST PALM BEACH AMENDMENT TO THE FBC, SECTION |
| | 107 WHICH REQUIRES THAT PLANS BE DRAWN AT NO LESS THAN |
| | 1/8? SCALE. (CITY AMENDMENT 107.2.1.4) |
| | 2. NEC 215.5 REQUIRES THAT YOU SUBMIT A COMPLETE |
| | FEEDER/RISER DIAGRAM INCLUSIVE OF LOAD CALCS AND |
| | CONDUCTOR SIZING. |
| | 3. NEC 215.6 REQUIRES THAT THE FEEDER/RISER DIAGRAM BE |
| | COMPLETE INCLUSIVE OF ALL GROUNDING. |
| | 4. NEC 408.4(A) REQUIRES THAT YOU PROVIDE A CIRCUIT |
| | DIRECTORY FOR EVERY PANEL. THE CIRCUIT DIRECTORY FOR |
| | PANEL ?P? DOES NOT MATCH YOUR RISER DIAGRAM WITH |
| | RELATION TO PANEL ?P2?. |
| | 5. NEC 408.4(B) REQUIRES THAT ALL NON-RESIDENTIAL |
| | PANELS BE MARKED TO INDICATE THE LOCATION OF ORIGIN OF |
| | THE POWER TO THE PANEL. |
| | 6. NEC 110.16 REQUIRES THAT ALL PANELS BE MARKED WITH |
| | AN ARC-FLASH HAZARD WARNING LABEL. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU |
| | |