2015-10-14 10:00:39PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE ELECTRICAL REVIEW OF THE
 ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH
 REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE
 REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED
 SHALL BE RESUBMITTED FOR ANOTHER REVIEW.
 1. FOR THE FUTURE, I DON?T KNOW IF YOU ARE AWARE OF A
 CITY OF WEST PALM BEACH AMENDMENT TO THE FBC, SECTION
 107 WHICH REQUIRES THAT PLANS BE DRAWN AT NO LESS THAN
 1/8? SCALE. (CITY AMENDMENT 107.2.1.4)
 2. NEC 215.5 REQUIRES THAT YOU SUBMIT A COMPLETE
 FEEDER/RISER DIAGRAM INCLUSIVE OF LOAD CALCS AND
 CONDUCTOR SIZING.
 3. NEC 215.6 REQUIRES THAT THE FEEDER/RISER DIAGRAM BE
 COMPLETE INCLUSIVE OF ALL GROUNDING.
 4. NEC 408.4(A) REQUIRES THAT YOU PROVIDE A CIRCUIT
 DIRECTORY FOR EVERY PANEL. THE CIRCUIT DIRECTORY FOR
 PANEL ?P? DOES NOT MATCH YOUR RISER DIAGRAM WITH
 RELATION TO PANEL ?P2?.
 5. NEC 408.4(B) REQUIRES THAT ALL NON-RESIDENTIAL
 PANELS BE MARKED TO INDICATE THE LOCATION OF ORIGIN OF
 THE POWER TO THE PANEL.
 6. NEC 110.16 REQUIRES THAT ALL PANELS BE MARKED WITH
 AN ARC-FLASH HAZARD WARNING LABEL.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  