2015-10-13 14:31:17BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15090200
 ADD: 2201 S. OLIVE AVE.
 CONT: AMERICAN HOME CARE
 TEL: (954)646-2283
 E-MAIL: AHCBUILDER@YAHOO
  
 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: WED. OCT. 07/ 2015
 ACTION: DENIED
  
 1) THE SUBMITTED ENGINEERING FOR ROOF ZONES 1, 2 & 3
 ARE IN CORRECT. THEY ARE INDICATED AS A EXPOSURE C. THE
 ENGINEERED LETTER SUBMITTED IS FOR THE NAILING PATTERN
 FOR THE 5/8 INCH ROOF SHEATHING TO THE WOOD FRAMING,
 NOT FOR THE NAILING OF THE BASE SHEET IN ZONES 2 & 3
 FOR A MECHANICALLY FASTENED ROOF SYSTEM. WILL REQUIRE
 CALCULATION RAS 117 PER THE SUBMITED NOA. SEE COMMENTS
 FROM 2ND REVIEW AS WELL.
  
 2ND REVIEW COMMENTS. THE PRESSURES FOR ROOF ZONE #1 OF
 -42.2 WOULD BE FOR A MEAN ROOF HEIGHT OF 25 FT.
 THE PRESSURES FOR ROOF ZONE #2 OF -57.4 WOULD BE FOR A
 MEAN ROOF HEIGHT OF ARE LOW FOR A MEAN ROOF HEIGHT OF
 15 FT. TABLES STAT AT 15 FT. FROM GRADE.
 THE PRESSURES FOR ROOF ZONE #3 OF -79.7 WOULD BE FOR A
 MEAN ROOF HEIGHT OF 15 FT EXPOSURE B.
 PLEASE REVISE PRESSURES.
  
 THE DESIGNER OF RECORD STILL HAS NOT PROVIDED RAS 117
 CALCULATIONS FOR FASTENING OF THE BASE SHEET TO THE
 ROOF SHEATHING.
  
  
  
  
  
  
  
  
  
 1ST REVIEW COMMENTS. THE PERMIT DESCRIPTION INDICATES
 THE REMOVAL & REPLACEMENT OF A FLAT ROOF. THE
 CONTRACTOR SUBMITTED A MIAMI-DADE NOA 14-0611.01 GAF
 RUBEROID MODIFIED BITUMEN ROOF SYSTEM FOR WOOD DECK.
 SYSTEMCIRCLED FOUND ON PAGE 27 OF 29.
 MEMBRANE TYPE: APP/SBS HEAT WELD
 DECK TYPE: 1
 DECK DESCRIPTION: 19/32 INCH OR GREATER PLYWOOD OR WOOD
 PLANK DECK
 SYSTEM YYPEE(2)
 ALL GENERAL AND SYSTEM LIMITATIONS SHALL APPLY.
 MAXIMUM DESIGN PRESSURE -52.5 PSF. SEE GENERAL
 LIMITATION # 7.
 PAGE 29 LIMITATION # 7 REQUIRES ENHANCED FASTENING IN
 ZONES 2 AND 3 BY A DESIN PROFESSIONAL, EITHER A FLORIDA
 ENGINEER OR FLORIDA ARCHITECT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved