| 2015-09-22 08:10:56 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15090200 |
| | ADD: 2201 S. OLIVE AVE. |
| | CONT: AMERICAN HOME CARE |
| | TEL: (954)646-2283 |
| | E-MAIL: AHCBUILDER@YAHOO |
| | |
| | 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: TUES. SEPT. 22/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) THE SUBMITTED ENGINEERING FOR ROOF ZONES 1, 2 & 3 |
| | ARE IN CORRECT. THEY ARE INDICATED AS A EXPOSURE C. |
| | THE PRESSURES FOR ROOF ZONE #1 OF -42.2 WOULD BE FOR A |
| | MEAN ROOF HEIGHT OF 25 FT. |
| | THE PRESSURES FOR ROOF ZONE #2 OF -57.4 WOULD BE FOR A |
| | MEAN ROOF HEIGHT OF ARE LOW FOR A MEAN ROOF HEIGHT OF |
| | 15 FT. TABLES STAT AT 15 FT. FROM GRADE. |
| | THE PRESSURES FOR ROOF ZONE #3 OF -79.7 WOULD BE FOR A |
| | MEAN ROOF HEIGHT OF 15 FT EXPOSURE B. |
| | PLEASE REVISE PRESSURES. |
| | |
| | THE DESIGNER OF RECORD STILL HAS NOT PROVIDED RAS 117 |
| | CALCULATIONS FOR FASTENING OF THE BASE SHEET TO THE |
| | ROOF SHEATHING. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | 1ST REVIEW COMMENTS. THE PERMIT DESCRIPTION INDICATES |
| | THE REMOVAL & REPLACEMENT OF A FLAT ROOF. THE |
| | CONTRACTOR SUBMITTED A MIAMI-DADE NOA 14-0611.01 GAF |
| | RUBEROID MODIFIED BITUMEN ROOF SYSTEM FOR WOOD DECK. |
| | SYSTEMCIRCLED FOUND ON PAGE 27 OF 29. |
| | MEMBRANE TYPE: APP/SBS HEAT WELD |
| | DECK TYPE: 1 |
| | DECK DESCRIPTION: 19/32 INCH OR GREATER PLYWOOD OR WOOD |
| | PLANK DECK |
| | SYSTEM YYPEE(2) |
| | ALL GENERAL AND SYSTEM LIMITATIONS SHALL APPLY. |
| | MAXIMUM DESIGN PRESSURE -52.5 PSF. SEE GENERAL |
| | LIMITATION # 7. |
| | PAGE 29 LIMITATION # 7 REQUIRES ENHANCED FASTENING IN |
| | ZONES 2 AND 3 BY A DESIN PROFESSIONAL, EITHER A FLORIDA |
| | ENGINEER OR FLORIDA ARCHITECT. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |