2016-03-07 16:50:12****PROVISO****
 ****REVISION REQUIRED SUBJECT TO FIELD INSPECTOR'S
 DISCRETION****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 A BUCK DETAIL IS REQUIRED. WINDOW AND DOOR INSTALLATION
 METHOD PROPOSED IS NOT CLEAR AS THE BUCK SPEC WAS NOT
 PROVIDED, AND THE PRODUCT APPROVALS DO NOT INCLUDE
 STEEL SUBSTRATE. A REVISION (STRUCTURAL BUCK
 SPECIFICATION OR ENGINEERED WINDOW INSTALLATION INTO
 STEEL SUBSTRATE) MAY BE REQUIRED SUBJECT TO INSPECTOR'S
 DISCRETION.
  
 THE WALL DETAIL STUCCO SPECIFICATION IS NOT IN
 COMPLIANCE WITH FBC 5TH EDITION RESIDENTIAL 703.6. NO
 BARRIER IS SHOWN BETWEEN THE STUCCO AND PLYWOOD, NOT
 CLEAR WHETHER OR NOT A BOND BREAK IS PROPOSED. PROVISO;
 VAPOR BARRIER AND PAPERBACK LATHE REQUIRED BETWEEN
 PLYWOOD SHEATHING AND STUCCO. DEVIATION FROM THIS
 SPECIFICATION MAY REQUIRE A REVISION, SUBJECT TO THE
 INSPECTOR'S DISCRETION.
  
 BASED ON THE STRUCTURAL DETAIL FOR THE WALL, IT APPEARS
 THAT A STRUCTURAL MULLION MAY BE REQUIRED. PRIOR TO
 INSPECTION, HIGHLIGHT THE PROPOSED INSTALLATION METHOD
 FOR THE WINDOW AND DOOR. IF A MULLION IS REQUIRED,
 PROVIDE AT INSPECTION WITH THE INSTALLATION DETAILS
 HIGHLIGHTED. SUBJECT TO INSPECTOR'S DISCRETION, A
 REVISION MAY BE REQUIRED.
  
  
  
  