| Plan Review Notes For Permit 15090199 |
| Permit Number |
15090199 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2016-03-07 16:50:12 | ****PROVISO**** | | | ****REVISION REQUIRED SUBJECT TO FIELD INSPECTOR'S | | | DISCRETION**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | A BUCK DETAIL IS REQUIRED. WINDOW AND DOOR INSTALLATION | | | METHOD PROPOSED IS NOT CLEAR AS THE BUCK SPEC WAS NOT | | | PROVIDED, AND THE PRODUCT APPROVALS DO NOT INCLUDE | | | STEEL SUBSTRATE. A REVISION (STRUCTURAL BUCK | | | SPECIFICATION OR ENGINEERED WINDOW INSTALLATION INTO | | | STEEL SUBSTRATE) MAY BE REQUIRED SUBJECT TO INSPECTOR'S | | | DISCRETION. | | | | | | THE WALL DETAIL STUCCO SPECIFICATION IS NOT IN | | | COMPLIANCE WITH FBC 5TH EDITION RESIDENTIAL 703.6. NO | | | BARRIER IS SHOWN BETWEEN THE STUCCO AND PLYWOOD, NOT | | | CLEAR WHETHER OR NOT A BOND BREAK IS PROPOSED. PROVISO; | | | VAPOR BARRIER AND PAPERBACK LATHE REQUIRED BETWEEN | | | PLYWOOD SHEATHING AND STUCCO. DEVIATION FROM THIS | | | SPECIFICATION MAY REQUIRE A REVISION, SUBJECT TO THE | | | INSPECTOR'S DISCRETION. | | | | | | BASED ON THE STRUCTURAL DETAIL FOR THE WALL, IT APPEARS | | | THAT A STRUCTURAL MULLION MAY BE REQUIRED. PRIOR TO | | | INSPECTION, HIGHLIGHT THE PROPOSED INSTALLATION METHOD | | | FOR THE WINDOW AND DOOR. IF A MULLION IS REQUIRED, | | | PROVIDE AT INSPECTION WITH THE INSTALLATION DETAILS | | | HIGHLIGHTED. SUBJECT TO INSPECTOR'S DISCRETION, A | | | REVISION MAY BE REQUIRED. | | | | | | | | | | | | |
|