Plan Review Notes
Plan Review Notes For Permit 15090199
Permit Number 15090199
Review Stop B
Sequence Number 3
Notes
Date Text
2016-02-03 13:59:25****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 COMMENTS FROM PREVIOUS LIST NOT ADDRESSED.
 PAGES/DETAILS FROM PRESCRIPTIVE DESIGN NOT PROVIDED
 (SEE SUGGESTIONS IN PLAN REVIEW), CALCULATIONS TO
 JUSTIFY THE DESIGN PROPOSED NOT PROVIDED, AND
 STRUCTURAL FRAMING DETAILS REQUESTED WERE NOT PROVIDED.
 PLEASE DO NOT RESUBMIT WITHOUT THIS INFORMATION.
 (CALCULATIONS MAY BE REQUIRED ONLY IF ASCE7-10 IS USED
 FOR DESIGN - AT THIS POINT, APPLICANT HAS ELECTED TO
 USE A PRESCRIPTIVE DESIGN. IF THIS CHANGES TO ASCE7-10,
 BE ADVISED THAT CALCULATIONS TO DEMONSTRATE THAT THE
 PROPOSED DESIGN COMPLIES WITH THE WIND DESIGN STATED
 MAY BE REQUIRED.)
  
 1. PLAN TO INCLUDE WIND DESIGN CRITERIA FBC 5TH ED.
 RESIDENTIAL 301.
  
 EXPOSURE STATED IS B, THIS IS EXPOSURE C, SEE AERIALS
 AND DEFINITION IN ASCE7 10.
  
 WIND SPEED NOT CLEAR; 250MPH AND 175 MPH STATED. ONE
 WIND SPEED TO BE APPLICABLE. COMPLIANCE WITH WIND
 DESIGN CRITERIA STATED WILL BE REQUIRED. 170MPH,
 EXPOSURE C, IMPORTANCE FACTOR II APPEARS TO BE
 APPLICABLE FOR THIS PROJECT.
  
 DESIGNER HAS DECLARED IMPORTANCE FACTOR I. THIS DOES
 NOT APPEAR APPROPRIATE AS, ONCE FULLY ENCLOSED, FAILURE
 OF THE DESIGN WILL BE HARMFUL TO ANYONE IN THE
 STRUCTURE. IT IS SUGESTED TO DESIGN TO IMPORTANCE
 FACTOR II OR PROVIDE RATIONALE (FOR IMPORTANCE FACTOR
 I) FOR BUILDING OFFICIAL CONSIDERATION. IF APPLICANT
 WISHES TO DESIGN TO IMPORTANCE FACTOR I, THAT RATIONALE
 IS TO BE SENT VIA EMAIL AND APPROVED PRIOR TO
 RESUBMITTAL.
  
 METHOD OF DESIGN NOT STATED. PRESCRIPTIVE IS NOT A
 DESIGN METHOD. SEE FBC 5TH EDITION RESIDENTIAL 301 FOR
 THE PRESCRIPTIVE OPTIONS AVAILABLE. IT APPEARS THAT
 THIS IS STEEL, SO THE STEEL PRESCRIPTIVE METHOD WOULD
 LIKELY BE APPLICABLE (AISI S230 07/S2 08).
  
 IF A PRESCRIPTIVE METHOD IS USED, PROVIDE DETAILS FROM
 THE PRESCRIPTIVE GUIDE. THIS STANDARD APPEARS TO BE
 AVAILABLE FOR FREE ON THE INTERNET. THIS IS NOT A
 GUARANTEE THAT THE WIND SPEED APPLICABLE FOR OUR AREA
 AND DESIGN SPECIFIC TO YOUR PROJECT, BUT IT IS
 SUGGESTED THAT YOU INVESTIGATE THIS GUIDE FOR DESIGN TO
 OBTAIN THE REQUIRED DETAILS.
  
 A STRUCTURAL FRAMING DETAIL IS REQUIRED.
  
 A BUCK DETAIL IS REQUIRED. A DETAIL WAS PROVIDED BUT
 BUCK SPECIFICATION NOT PROVIDED.
  
 A SPECIFICATION FOR FASTENING INTO FLOOR AND COLUMN,
 BUT NOT THE HEADER, AND IT IS NOT CLEAR HOW THIS DESIGN
 WAS DETERMINED AND HOW DESIGNER HAS DETERMINED THAT
 THIS MEETS THE WIND RESISTANCE REQUIREMENTS.
  
 BUCK STRUCTURAL SPECIFICATION WAS NOT PROVIDED). FBC
 5TH ED RESIDENTIAL 301.
  
 ELEVATION INFORMATION WAS NOT PROVIDED (RELATIVE TO
 FINISHED FLOOR IN EXISTING STRUCTURE, RELATIVE TO
 GRADE); PLEASE INCLUDE ON REVISED PLANS. THE PLAN
 STATES THAT THE EXISTING GRADE WILL NOT CHANGE AND THAT
 THE FLOOR WOULD REMAIN. SEE FBC 5TH EDITION RESIDENTIAL
 318.7, 6 INCHES REQUIRED BETWEEN THE EXTERIOR WALL
 COVERINGS AND FINAL EARTH GRADE. PROVIDE A DETAIL WHICH
 SHOWS COMPLIANCE. IT IS POSSIBLE THAT THE FINISHED
 FLOOR ELEVATION WILL BE REQUIRED TO BE RAISED (BUT NOT
 POSSIBLE TO DETERMINE AT THIS TIME DUE TO LACK OF
 INFORMATION).
  
 THE WALL DETAIL STUCCO SPECIFICATION IS NOT IN
 COMPLIANCE WITH FBC 5TH EDITION RESIDENTIAL 703.6. NO
 BARRIER IS SHOWN BETWEEN THE STUCCO AND PLYWOOD, NOT
 CLEAR WHETHER OR NOT A BOND BREAK IS PROPOSED, NUMBER
 OF STUCCO COATS NOT STATED. A COMPLETE REVIEW OF THE
 STUCCO SPEC WILL BE DONE WHEN SUBMITTED (AT THIS TIME
 NOT SURE IF THE THICKNESS PROPOSED COMPLIES WITH THE
 REQUIREMENTS OF ASTM C 926 AND ASTM C 1063).
  
 SEE FBC 5TH EDITION EXISTING BUILDING CODE SECTION
 301.1, REVISE PLAN TO INDICATE METHOD OF COMPLIANCE
 SELECTED.
  
 REVISE PLAN TO SHOW ROOMS WHICH OPEN INTO THE PROPOSED
 ENCLOSED PORCH (PROVIDE ROOM DESIGNATIONS SUCH AS
 LIVING ROOM, KITCHEN, BEDROOM). IF BEDROOMS ARE
 AFFECTED, PLEASE ADVISE AS ADDITIONAL INFORMATION WILL
 BE REQUIRED.
  
  
  
  
  
  