Plan Review Notes
Plan Review Notes For Permit 15090199
Permit Number 15090199
Review Stop B
Sequence Number 2
Notes
Date Text
2015-11-03 08:54:52****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST:
  
 1. PLAN TO INCLUDE WIND DESIGN CRITERIA FBC 5TH ED.
 RESIDENTIAL 301. THIS IS TO INCLUDE WIND SPEED, RISK
 CATEGORY, EXPOSURE CLASSIFICATION, AND METHOD OF
 DESIGN. IF A PRESCRIPTIVE METHOD IS USED, PROVIDE
 DETAILS FROM THE PRESCRIPTIVE GUIDE. IF ENGINEERING IS
 USED (ASCE7-10), PROVIDE CALCULATIONS. PLANS TO INCLUDE
 ALL STRUCTURAL INFORMATION (AND, IF NOT SEALED BY A
 DESIGN PROFESSIONAL, CALCULATIONS AS APPLICABLE) AND
 ADEQUATE INFORMATION ABOUT THE PROPOSED IMPROVEMENT. NO
 ELEVATION INFORMATION WAS PROVIDED (RELATIVE TO
 FINISHED FLOOR IN EXISTING STRUCTURE, RELATIVE TO
 GRADE); PLEASE INCLUDE ON REVISED PLANS.
  
 A STRUCTURAL FRAMING DETAIL IS REQUIRED. IT APPEARS
 THAT METAL FRAMING IS PROPOSED; IT IS NOT CLEAR HOW THE
 IMPACT WINDOWS WILL BE INSTALLED (DIRECTLY INTO
 FRAMING? INTO BUCKS? NO BUCK DETAIL PROVIDED). FBC 5TH
 ED RESIDENTIAL 301.
  
 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 COMPONENTS AND CLADDING, FAC9N-3, FBC 5TH ED.
 RESIDENTIAL 301. A WINDOW PRODUCT APPROVAL WAS
 PROVIDED, BUT I COULD NOT LOCATE A DOOR PRODUCT
 APPROVAL. (I DID NOT GO THROUGH EVERY PAGE PROVIDED AS
 THERE WERE ABOUT 50 8.5"X11" SPEC SHEETS PROVIDED WHICH
 ARE NOT NEEDED FOR PLAN REVIEW).
  
 2ND REVIEW, NOT ADDRESSED. IT APPEARS THAT IMPACT
 WINDOWS ARE PROPOSED. PRODUCT APPROVALS NOT PROVIDED.
  
 3. WHEN RESUBMITTING, PROVIDE TWO COMPLETE COLLATED
 SETS OF PLANS FOR PERMIT ISSUANCE.