| Date |
Text |
| 2015-09-19 12:31:11 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. MANY UNNUMBERED 8.5"X11" PAGES WERE SUBMITTED. SPEC |
| | SHEETS FOR EACH COMPONENT OF THE PROJECT ARE NOT |
| | REQUIRED. PLANS ARE TO BE ARCHITECTURAL QUALITY, TO |
| | SCALE, PLEASE SEE FBC 107.2.1: |
| | |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE |
| | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| | ELECTRONIC MEDIA DOCUMENTS SHALL BE |
| | SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN |
| | DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS |
| | CODE AND RELEVANT LAWS, ORDINANCES, RULES |
| | AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE |
| | QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL |
| | CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| | OR IN PART, NOR SHALL THE TERM "LEGAL" OR |
| | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5). |
| | |
| | 2. PLAN TO INCLUDE WIND DESIGN CRITERIA FBC 5TH ED. |
| | RESIDENTIAL 301. THIS IS TO INCLUDE WIND SPEED, RISK |
| | CATEGORY, EXPOSURE CLASSIFICATION, AND METHOD OF |
| | DESIGN. IF A PRESCRIPTIVE METHOD IS USED, PROVIDE |
| | DETAILS FROM THE PRESCRIPTIVE GUIDE. IF ENGINEERING IS |
| | USED (ASCE7-10), PROVIDE CALCULATIONS. PLANS TO INCLUDE |
| | ALL STRUCTURAL INFORMATION (AND, IF NOT SEALED BY A |
| | DESIGN PROFESSIONAL, CALCULATIONS AS APPLICABLE) AND |
| | ADEQUATE INFORMATION ABOUT THE PROPOSED IMPROVEMENT. NO |
| | ELEVATION INFORMATION WAS PROVIDED (RELATIVE TO |
| | FINISHED FLOOR IN EXISTING STRUCTURE, RELATIVE TO |
| | GRADE); PLEASE INCLUDE ON REVISED PLANS. |
| | |
| | 3. PROVIDE A FLOOR PLAN TO SHOW IF ANY SLEEPING |
| | ROOMS/EMERGENCY MEANS OF ESCAPE AND RESCUE ARE AFFECTED |
| | BY THE PROPOSED RENOVATION, FBC 107, FBC R310, FBC EB |
| | 704.1. |
| | |
| | 4. WINDOW PRODUCT APPROVALS PROVIDED ARE NON IMPACT. |
| | IMPACT PROTECTION REQUIRED, FBC R 301.2.1.2. PROVIDE |
| | PRODUCT APPROVALS AND, IF SHUTTERS ARE USED, COMPLETE |
| | THE SAMPLE INSTALLATION SCHEDULE (AVAILABLE IN THE |
| | LOBBY AND AT: |
| | |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/SCHEDULE_FOR_INSTALLATION.PDF |
| | |
| | 5. IT APPEARS THAT THE EXISTING SUNROOM IS BEING |
| | CONVERTED TO HABITABLE SPACE. REVISE FLOOR PLAN TO |
| | PROVIDE A ROOM DESIGNATION, FBC 107. IMPACT FEE |
| | ASSESSMENT BY PALM BEACH COUNTY MAY BE REQUIRED. |
| | |
| | 6. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR |
| | COMPONENTS AND CLADDING, FAC9N-3, FBC 5TH ED. |
| | RESIDENTIAL 301. A WINDOW PRODUCT APPROVAL WAS |
| | PROVIDED, BUT I COULD NOT LOCATE A DOOR PRODUCT |
| | APPROVAL. (I DID NOT GO THROUGH EVERY PAGE PROVIDED AS |
| | THERE WERE ABOUT 50 8.5"X11" SPEC SHEETS PROVIDED WHICH |
| | ARE NOT NEEDED FOR PLAN REVIEW). |
| | |
| | 7. A COMPLETE PLAN REVIEW CANNOT BE DONE AT THIS TIME, |
| | FBC 107. OTHER REVIEWS (SUCH AS MECHANICAL, ELECTRICAL) |
| | AND INFORMATION (ENERGY CALCS) MAY BE REQUIRED AFTER |
| | SCOPE IS CLARIFIED. |
| | |
| | |
| | |