| Notes |
| Date |
Text |
| 2015-09-29 14:39:37 | 1) SIZE THE SCUPPERS AND DOWNSPOUTS FOR THE ADDITION. | | | COMPLY WITH 2014 FBC- RESIDENTIAL SEC.R 903.4. | | | 2) PROVISIONS SHALL BE MADE FOR OVERFLOW | | | DRAINS/SCUPPERS PER THE 2014 FBC-RESIDENTIAL SEC. | | | R903.4.1 & FBC-PLUMBING TABLE 1106.7 | | | 3) SHOW THE WIDTH OF THE SHOWER IN THE NEW POOL BATH. | | | THE SHOWER SHALL BE A MIN. OF 30 INCHES IN WIDTH AND A | | | MINIMUM OF 900 SQUARE INCHES. 2014 FBC-RES. | | | SEC.P2708.1. | | | 4) CLARIFY IF THERE IS A LAUNDRY TRAY IN THE LAUNDRY | | | ROOM. IT APPEARS THAT THERE IS. IF SO, IT SHALL BE | | | SHOWN ON THE SANITARY RISER. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|