2015-10-27 12:15:14RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE: THESE COMMENTS APPLY TO PERMIT NUMBERS 15090189
 AND 15090192.
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 2- SHEET A100: IDENTIFY WHAT'S IN THE NEW LAUNDRY AREA
 AND NEW MUD ROOM. THERE ARE NO NAMES FOR THE STAFF
 DRAWN ON THE FLOOR PLAN. IDENTIFY EVERYTHING THAT IS
 DRAWN IN THE NEW LAUNDRY AREA AND NEW MUD ROOM. SEC.
 107.2.1 CITY AMENDMENTS.
  
 3- SHEET A101:
 A) DOWNSPOUTS SHOWN ON ALL EXTERIOR ELEVATIONS TO
 COMPLY WITH SEC. R318.5 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014). REVISE ELEVATIONS AS REQUIRED.
  
 B) REVISE HEIGHT OF HANDRAIL SHOWN ON THE EAST
 ELEVATION TO COMPLY WITH SEC. R311.7.8.1 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION AND INSTALLATION OF NEW TERRACE GUARDRAILS
 SHOWING COMPLIANCE WITH THE LIVE LOADS OF TABLE R301.5
 OF FBC-RESIDENTIAL, 5TH EDITION (2014) AND WITH THE
 SPECIFICATIONS OF SEC. R312 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 4- SHEET A102:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 VENTILATION AND ACCESS FOR THE UNDER FLOOR SPACE AT NEW
 LAUNDRY/BATHROOM AREA SHOWING COMPLIANCE WITH SEC. R408
 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 B) DOWNSPOUTS SHOWN ON ALL EXTERIOR ELEVATIONS TO
 COMPLY WITH SEC. R318.5 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014). REVISE ELEVATIONS AS REQUIRED.
  
 5- SPECIFY VENTILATION FOR THE NEW GARAGE/OFFICE
 ADDITION AND FOR THE NEW LAUNDRY/BATHROOM ADDITIONS
 SHOWING COMPLIANCE WITH SEC. R806 OF FBC-RESIDENTIAL,
 5TH EDITION (2014). IF DESIGNING AN UNVENTED ATTIC,
 THEN PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 SHOWING COMPLIANCE WITH SEC. R806.5 OF FBC-RESIDENTIAL,
 5TH EDITION (2014). IF USING ICYNENE OR ANY OTHER FOAM
 INSULATION, THEN PROVIDE MANUFACTURER'S SPECS REVIEWED
 IN WRITING BY THE ARCHITECT OF RECORD.
 NOTE: COORDINATE WITH ENERGY CALCULATIONS TO AVOID
 CONFLICTS OR DELAYS.
  
 6- PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE R-11
 INSULATION SPECIFIED ON WALL SECTION 1 ON SHEET A103
 AND WALL TYPES ON SHEET A104. SEC. R103.2 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 NOTE: COORDINATE WITH ENERGY CALCULATIONS TO AVOID
 CONFLICTS OR DELAYS.
  
 7- SHEET A104: R-VALUE INSULATION SHOWN ON DOORS AND
 WINDOWS DETAILS TO MATCH R-VALUE SHOWN ON THE WALL
 TYPES. SEC. 107.2.1 CITY AMENDMENTS. NOTE: COORDINATE
 WITH ITEM #7 ABOVE.
  
 8- PROVIDE DETAILS AND SPECIFICATIONS FOR CEILING
 ASSEMBLY BETWEEN GARAGE AND SECOND FLOOR OFFICE SHOWING
 COMPLIANCE WITH INSULATION SPECIFIED ON THE ENERGY
 CALCULATIONS. . SEC. R103.2 OF FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
 NOTE: COORDINATE WITH ENERGY CALCULATIONS TO AVOID
 CONFLICTS OR DELAYS.
  
 9- NEW LAUNDRY/BATHROOM ADDITION ON SHEET S-1: CLARIFY
 FLOOR FRAMING WITH 2X10 PT WOOD JOISTS AND 6" RECESS
 FOR NEW SHOWER. SEC. 107.2.1 CITY AMENDMENTS.
  
 10- ENGINEER TO PROVIDE DESIGN PRESSURES FOR WINDOWS
 AND DOORS. WINDOWS AND DOORS DESIGN PRESSURES SHOWN ON
 THE EXTERIOR ELEVATIONS DON'T CORRESPOND TO THE
 EXPOSURE "C" AND HEIGHT SPECIFIED BY THE ENGINEER ON
 SHEET S-3. SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 11- ENERGY CALCULATIONS SUBMITTED FOR THE NEW
 LAUNDRY/BATHROOM ADDITION:
 NOTE: COORDINATE PLANS AND ENERGY CALCULATIONS TO AVOID
 CONFLICTS OR DELAYS.
  
 A) FLOOR INFORMATION ON ITEM #8 DOESN'T MATCH PLANS.
 REVISE AS REQUIRED. SEC. R103.2 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 B) WALL INFORMATION ON ITEM #9 DOESN'T MATCH PLANS.
 REVISE AS REQUIRED. SEC. R103.2 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 NOTE: LABELS FOR DOORS AND WINDOWS U-FACTOR AND SHGC
 FACTORS SPECIFIED ON THE ENERGY CALCULATIONS WILL BE
 REQUIRED FOR INSPECTION.
  
 12- ENERGY CALCULATIONS SUBMITTED FOR THE NEW
 GARAGE/OFFICE:
 NOTE: COORDINATE PLANS AND ENERGY CALCULATIONS TO AVOID
 CONFLICTS OR DELAYS.
  
 A) CEILING INFORMATION ON ITEM #10 DOESN'T MATCH PLANS.
 PLANS DON'T SHOW VENTED ATTIC. SEC. R103.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) PROVIDE INFORMATION FOR THE HOT WATER SYSTEM. SEC.
 R103.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 C) THERE IS NOT KITCHEN ON PLANS. REVISE AS REQUIRED.
 SEC. R103.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 D) CLARIFY WHY ARE THERE ARE 6 OCCUPANTS IN THIS HOME
 OFFICE?. ARE THERE 6 OCCUPANTS AT ALL TIMES?. THE CODE
 DOESN'T ALLOW ANY FACTOR EXTRA FACTORS THAT WILL AFFECT
 THE EQUIPMENT SIZING. SEC. 403.6.1 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 E) CLARIFY WHY THERE IS NOT R-VALUE ON THE FLOOR
 INFORMATION ON PAGE 2 OF 4. ALSO, THE FINISH FLOOR IS
 WOOD NOT CARPET. REVISE AS REQUIRED. SEC. R103.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 F) ROOF INFORMATION ON PAGE 2 OF 4 DOESN'T MATCH PLANS.
 SEC. R103.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 G) ATTIC AND CEILING INFORMATION ON PAGE 2 OF 4 DOESN'T
 MATCH PLANS. ATTIC IS NOT VENTED. SEC. R103.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 H) INSULATED DOOR SHOWN ON PAGE 3 OF 4 DOESN'T MATCH
 PLANS AND PRODUCT APPROVALS SUBMITTED. SEC. R103.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 I) WINDOWS INFORMATION SHOWN ON PAGE 3 OF 4 DOESN'T
 MATCH PLANS. REVISE GLASS SQUARE FOOTAGE ON EACH
 BUILDING ORIENTATION TO MATCH PLANS. AND MISSING
 INFORMATION FOR WEST ELEVATION WINDOW. SEC. R103.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 J) REVISE WINDOWS OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. SEC. R103.2 OF FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 NOTE: LABELS FOR DOORS AND WINDOWS U-FACTOR AND SHGC
 FACTORS SPECIFIED ON THE ENERGY CALCULATIONS WILL BE
 REQUIRED FOR INSPECTION WHEN NOT USING THE DEFAULT
 NUMBERS INCORPORATED IN THE PROGRAM.
  
 13- ENGINEER OF RECORD DRAWING S-1 SPECIFIES MIN. 2500
 PSF SOIL BEARING CAPACITY REQUIRED.. SOIL TEST REPORT
 BY ARDAMAN & ASSOCIATES, INC. DISCUSSIONS AND
 RECOMMENDATIONS ON PAGE 3 SPECIFIES THAT FOUNDATIONS
 CAN BE PROPORTIONED FOR A MAXIMUM ALLOWABLE BEARING
 STRESS OF 2,000 PSF. THIS DISCREPANCY TO BE COORDINATED
 BY ENGINEER OF RECORD AND GEOTECHNICAL ENGINEER. REVISE
 AS REQUIRED TO MATCH. SEC. R301 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 14- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) HOME OFFICE INSWING ENTRY DOOR AS SHOWN ON PLANS.
  
 B) RECYCLED SINGLE HUNG WINDOW SHOWN ON PLANS FOR THE
 NEW BATHROOM.
  
 C) RECYCLED FIXED FRENCH DOORS SHOWN ON PLANS FOR THE
 NEW LAUNDRY AREA AND MUD ROOM AREA.
  
 D) MODIFIED BITUMEN FOR FLAT ROOFS. AND, CLEARLY
 IDENTIFY APPROVED ASSEMBLY AND PROVIDE SIGNED AND
 SEALED RAS 117 CALCULATIONS IF SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES REQUIRED BY SEC. R301
 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 E) MODIFIED BITUMEN FOR GARAGE/HOME OFFICE TERRACE THAT
 IS DESIGNED TO RECEIVE TILE AS SPECIFIED ON PLANS. AND,
 CLEARLY IDENTIFY APPROVED ASSEMBLY AND PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS IF SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES REQUIRED BY SEC. R301
 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 F) ALL SIMPSON OR USP STRUCTURAL CONNECTORS SPECIFIED
 ON PLANS AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR OR DESIGNER OF RECORD TO LIST THE FLORIDA
 PRODUCT APPROVAL NUMBER NEXT EACH SPECIFIED CONNECTOR.
  
 G) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 15- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 16- THERE ARE SEVERAL DOORS AND WINDOWS PRODUCT
 APPROVALS SUBMITTED. CLEARLY IDENTIFY PROPOSED LOCATION
 OF EACH DOOR AND WINDOW PRODUCT APPROVAL SUBMITTED. FOR
 EXAMPLE, LAUNDRY AREA, OFFICE, ETC. SEC. 107.2.1 CITY
 AMENDMENTS. CLARIFY WHERE IS FIXED WINDOW NOA
 14-0424.03 SUBMITTED GOING TO BE INSTALLED. PLANS DON'T
 SHOW ANY FIXED WINDOWS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 SUBMITT DETACHED OLD DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]